The Inline controller under PC Worx
6959_en_07
PHOENIX CONTACT
63
Syntax for entering TCP-based communication at the PARTNER input (example)
Please note that the syntax is case-sensitive and only insert one space between the
parameters.
If you do not specify any parameters, the default values will be used.
Minimum configuration:
/ACTIVE /PORT=502 /IP=172.16.100.35
/PASSIVE /PORT=502
Maximum configuration:
/ACTIVE /PORT=502 /IP=172.16.100.35 /CONTO=3000 /RCVTO=5000
/PASSIVE /PORT=502 /IP=172.16.100.35 /CONTO=3000 /RCVTO=5000
Parameters:
For TCP/IP connections between a controller and another TCP/IP-capable device, one
partner must be active and the other passive.
Parameter
Meaning
PASSIVE
If EN_C = TRUE:
It is expected that a communication partner establishes the connection.
If no IP address is specified for a device configured with “PASSIVE”, this device responds to
the first connection request that comes in.
If an IP address is specified, the device only responds to the request for the device with the
specified address.
ACTIVE
If EN_C = TRUE:
The Inline controller establishes the connection.
PORT=xxxx
Port address of the communication partner (decimal, 1
≤
port
≤
65535)
IP=www.xxx.yyy.zzz
IP address of the communication partner.
If no IP address is specified in “Passive” mode, the connection to the first partner that logs on
is accepted.
CONTO=xxxx
Connect timeout (in ms)
The default value for connection establishment confirmation is 3000 ms. After this time has
elapsed, another attempt to establish a connection (reconnect; close socket/open socket) is
automatically made.
The time can be changed using this parameter.
RCVTO=xxxx
Receive timeout (in ms)
The default value is 5000 ms. If no telegram is received within this time, the IP_URCV block
indicates an error.
Summary of Contents for ILC 330 Series
Page 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Page 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Page 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Page 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Page 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...