3.6.1
IP_CONNECT
This block is used to establish a connection between two communication partners via an IP
connection.
Figure 3-10
IP_Connect block
IP_CONNECT
EN_C
PARTNER
VALID
ERROR
STATUS
ID
7062B021
Table 3-12
IP_CONNECT function block inputs and outputs
Name
Data
type
Data direction
Description
EN_C
BOOL
Input
If you set this input to TRUE, the block will attempt to establish a connection
to the IP address specified under PARTNER. However, connection
establishment is only possible if the block is called at both communication
partners and both partners request communication establishment.
FALSE
The connection is aborted.
TRUE
The connection is established or maintained.
PARTNER
STRING
Input
This input specifies the communication partner to be used for communication.
•
Enter the partner IP address followed by some optional parameters.
•
Use the syntax specified below this table.
VALID
BOOL
Output
This output indicates whether a valid connection has been established.
Following successful connection establishment, the output is set to TRUE.
The output remains in the TRUE state as long as the connection is
established.
The returned communication connection ID must be transferred to the
IP_USEND and IP_URCV function blocks. You can connect the ID output of
the IP_CONNECT block directly to the ID input at the IP_USEND and
IP_URCV blocks.
ERROR
BOOL
Output
Rising edge: an error has occurred. The error code can be read at the
STATUS output during the cycle in which the rising edge occurs.
STATUS
INT
Output
Error codes of the error that occurred.
ID
INT
Output
Unique ID of the communication connection. If several communication
connections are established, the ID parameter can be used to distinguish
between them. ID is only valid if the VALID output = TRUE.
Summary of Contents for ILC 330 Series
Page 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Page 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Page 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Page 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Page 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...