onlinecomponents.com
UM EN ILC 1XX
5-6
PHOENIX CONTACT
7805_en_02
IEC 61131 runtime system
ILC 130 ETH
ILC 150 ETH
ILC 155 ETH,
ILC 170 ETH 2TX
Programming system
PC WorX
PC WorX
PC WorX
Speed
1.7 ms for 1 K
instructions, typical
1.5 ms for 1 K
instructions, typical
1.5 ms for 1 K
instructions, typical
Shortest cycle time (for cyclic task)
1 ms
1 ms
1 ms
Program memory
192 KB, 16 K
instructions in IL, typical
256 KB, 21 K
instructions in IL, typical
512 KB, 42 K
instructions in IL, typical
Data memory
192 KB
256 KB
512 KB
Memory for retentive data
8 KB NVRAM
8 KB NVRAM
48 KB NVRAM
Number of control tasks
8
8
8
Parameterization memory
Integrated (ILC 130 ETH, ILC 150 ETH, ILC 155 ETH)
Plug-in, SD card (ILC 170 ETH 2TX)
4 MB Flash memory
(100,000 write access
operations per sector,
typical)
–
4 MB Flash memory
(100,000 write access
operations per sector,
typical)
–
4 MB Flash memory
(100,000 write access
operations per sector,
typical)
256 MB (1,000,000
write access operations
per sector, typical), see
"Accessories" on
page 5-8
Please note that the number of write access operations to the parameterization memory is limited.
We recommend that you limit the number of write access operations on the parameterization memory in your application program by first
storing data on the data memory and/or the memory for retentive data (NVRAM). Write access operations on the parameterization memory
for small volumes of data (bit, byte) should not be possible in your application program. Data should only be transferred from the data
memory/memory for retentive data to the parameterization memory if the data memory/memory for retentive data is full, i.e., data must be
deleted first to enable further write access operations.
Realtime clock
Accuracy
1 minute/week, maximum
Power reserve
3 days
Ambient conditions
Degree of protection
IP20 (EN 60529:1991)
Permissible temperature (operation)
-25°C to +55°C
Permissible temperature (storage/transport)
-25°C to +85°C
Permissible humidity (operation/storage/transport)
10% to 95% according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 106 kPa (up to 3000 m above sea level)
Vibration
5g
This temperature range is only guaranteed if the Inline Controller is mounted horizontally.
Mechanical tests
Vibration resistance according to EN 60068-2-6, IEC 60068-2-6
Operation: 5g
Shock test according to EN 60068-2-27, IEC 60068-2-27
25g