Notes on using the Inline Controller
(ILC 150 ETH/ILC 155 ETH) in potentially explosive
areas
Approval according to EC Directive 94/9 (ATEX)
II 3G Ex nAC II T4 X
The Inline Controller (ILC 150 ETH/ILC 155 ETH) conforms to the requirements of
protection type "n" and can be installed in a zone 2 potentially explosive area. The Inline
Controller (ILC 150 ETH/ILC 155 ETH) is a category 3G item of electrical equipment.
Figure 2-4
Typical labeling of terminals for use in potentially explosive areas
1.
When working on the Inline Controller, always disconnect the supply voltage.
2.
The Inline Controller must only be installed, started up, and maintained by qualified
specialist personnel.
3.
Mount the Inline bus coupler in a control cabinet or metal housing. The minimum
requirement for both items is IP54 protection according to EN 60529.
4.
The Inline Controller must not be subject to mechanical strain and thermal loads, which
exceed the limits specified in the product documentation.
5.
The Inline Controller must not be repaired by the user. Repairs may only be carried out
by the manufacturer. The Inline Controller is to be replaced by an approved controller
of the same type.
6.
Only category 3G equipment may be connected to Inline Controllers in zone 2.
7.
Observe all applicable standards and national safety and accident prevention
regulations for installing and operating equipment.
WARNING: Explosion hazard
Only Inline terminals that are approved for use in potentially explosive areas may
be snapped onto the Inline Controller.
Before using an Inline terminal in a zone 2 potentially explosive area, first check that the
terminal has been approved for installation in this area.
For a list of terminals approved for zone 2 potentially explosive areas, please refer to the
AH EN IL EX ZONE 2 application note.
Check the labeling on the Inline terminal and the packaging (see Figure 2-4).
WARNING: Explosion hazard
Before startup, ensure that the following points and instructions are observed.
5561C001
INTERBUS
GL
UL
xx
Potential routing 4 A maximum
Potential routing 4 A maximum
for use in Ex areas
for use in Ex areas
II 3G Ex nAC IIC T4 X
II 3G Ex nAC IIC T4 X
LISTED
31ZN
Proc. Ctrl. Eqpt. For Haz. Locs.
Proc. Ctrl. Eqpt. For Haz. Locs.
Cl. I, Zn. 2, AEx nC IIC T5
Cl. I, Zn. 2, AEx nC IIC T5
Cl. I, Zn. 2, Ex nC IIC T5
Cl. I, Zn. 2, Ex nC IIC T5
Cl. I, Div. 2, Grp. A,B,C,D T5
Cl. I, Div. 2, Grp. A,B,C,D T5
IBx IL xx xx x
IBx IL xx xx x
Order-No.: xxxxxxx
Order-No.: xxxxxxx
Module-ID: xx HW/FW XX/-
Module-ID: xx HW/FW XX/-