onlinecomponents.com
UM EN ILC 1XX
2-34
PHOENIX CONTACT
7805_en_02
2.16
Digital inputs and outputs
There are eight 24 V DC inputs and four 24 V DC outputs.
Figure 2-24
Assignment of the terminal points of connectors 2 to 4
The descriptions for digital inputs and outputs apply to all the Inline Controllers listed on
the inner cover page of this manual.
AU
TO
MA
TIO
NW
OR
X
ILC
150
ETH
Order-No.:
2985330
HW/FW
: 00/100
MAC
Addr
.: xx.xx.xx.xx
UL
US
UM
I1
I3
I2
I4
I6
I5
I8
I7
RESET
E
Q2
Q1
Q3
Q4
1
PRG
FF
LN
K
AC
T
MRESET
RUN/PROG
ST
OP
FR
PF
RDY
FAIL
7805A011
1
2
1
2
3
4
1
2
3
4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
2 - 3
1
2
1
2
3
4
1
2
3
4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
4
Table 2-7
Terminal point assignment
Terminal point
Assignment
Remark
Connector 2
Output terminal points
1.1
Q1
Output 1
2.1
Q2
Output 2
1.2, 2.2
GND
Ground contact for 2 and 3-wire termination
1.3, 2.3
FE
Functional earth ground for 3-wire termination
1.4
Q3
Output 3
2.4
Q4
Output 4
Connector 3
Input terminal points
1.1
I1
Input 1
2.1
I2
Input 2
1.2, 2.2
24 V
Supply voltage U
M
for 2 and 3-wire termination
1.3, 2.3
GND
Ground contact for 3-wire termination
1.4
I3
Input 3
2.4
I4
Input 4
The outputs are supplied with 24 V DC from the segment supply (U