![Phoenix Contact AXC F 1152 Installing, Starting Up, And Operating Download Page 93](http://html1.mh-extra.com/html/phoenix-contact/axc-f-1152/axc-f-1152_installing-starting-up-and-operating_1551419093.webp)
Ordering data and technical data
107708_en_08
PHOENIX CONTACT
14.3
Technical data of the AXC F 1152 and AXC F 2152
Dimensions (nominal sizes in mm)
Width
45 mm
Height
126.93 mm
Depth
75 mm
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used
(in accordance with EN 60715).
45
75
123
126,93
General data
Color
Gray
Weight
215 g
Design
Axioline
Mounting method
DIN rail mounting
Operating system
Linux
RAM
512 MByte DDR3 SDRAM
Real-time clock
Yes
Ambient conditions
Ambient temperature (operation)
-25°C ... 60°C up to 2000 m above sea level (note derating)
-25°C ... 55°C up to 3000 m above sea level (note derating)
≤
55°C (with max. 1 A on U
Bus
)
>55°C ... 60°C (only in conjunction with an Axioline F power
module AXL F PWR 1H (Order No. 2688297))
Ambient temperature (storage/transport)
-40°C … 85°C
Permissible humidity (operation)
5% ... 95% (in accordance with DIN EN 61131-2)
Permissible humidity (storage/transport)
5% ... 95% (in accordance with DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
58 kPa ... 106 kPa (up to 4500 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Vibration (operation)
5g