AXC F X152
PHOENIX CONTACT
107708_en_08
Axioline F/
system and firmware
For system-specific information on the Axioline F system, please refer to the
PLCnext Engineer online help and the “Axioline F: System and installation”
(UM EN AXL F SYS INST) and “Axioline F: Diagnostic registers and error messages”
(UM EN AXL F SYS DIAG) user manuals.
The user manuals can be downloaded at
phoenixcontact.net/product/2404267
MRP (only AXC F 1152 and
AXC F 2152)
The MRP (Media Redundancy Protocol) can be used via the Ethernet interfaces of the con-
troller. The controller supports the MRP client function, which can be enabled or disabled
via an engineering tool (e.g., PLCnext Engineer). This function is disabled in delivery state.
If the function is enabled, it remains enabled after the supply voltage is switched off and on.
If the controller has been reset to the delivery state, the MRP client function will also be dis-
abled again. In a ring with Media Redundancy Protocol, maximum switch-over times of up
to 200 ms can be expected.
Parameterization
memory/SD card
The controllers have an internal parameterization memory. This memory can be used to
store programs and configurations which belong to your project, e.g., the visualization proj-
ect. If the internal parameterization memory is not large enough for your application, the
controllers can be operated using an SD card. The SD card is optional and not required to
operate the controllers.
Data buffering/backup in
the event of voltage
failures
In the event of a supply voltage failure, the AXC F 3152 saves control data, e.g., retain data
and log files, on the inserted parameterization memory (SD card).
The device firmware recognizes the voltage failure. The retain data (variables of the control-
ler that are marked as “Retain” in the PLCnext Engineer project) and log files are automati-
cally backed up on the parameterization memory.
Visualization
You can create visualizations for the controller using the HMI integrated in
PLCnext Engineer.
Real-time clock
In the event that the supply voltage fails, the real-time clock integrated in the controllers is
buffered, see
Section “Ordering data and technical data” on page 91
Function extensions using
PLCnext apps
You can easily extend the scope of functions of the controllers using apps from the
PLCnext Store.
.
The SD card is not included in the scope of delivery of the controller.
•
Only use an SD card provided by Phoenix Contact (see
).
NOTE: Damage to the SD card after formatting
The SD card is already formatted (ext4 format) and is intended for use with
Phoenix Contact controllers of the PLCnext Control product family. If you format the SD
card, certain information on the SD card that is required for use with Phoenix Contact de-
vices will be lost. After formatting, you can no longer use the SD card to operate the con-
troller.
•
Ensure that the SD card is not formatted.
NOTE: Startup of the AXC F 3152 not ensured
For proper startup of the device, the supply voltage may be switched on at the earliest 30
seconds after the diagnostic and status indicators go out.