OccuSwitch DALI
User Guide
Page 46
95
Check if the slave is in reset state
YES/NO
x
96
Check if the slave is missing a short address
YES/NO
x
97
Returns the version number as
XX
XX
x
98
Returns the content of the DTR as
XX
XX
x
99
Returns the device type as
XX
XX
x
Answer is 1
9A
Returns the physical minimum level as
XX
XX
x
1% is NOT related to DALI drivers connected to OSD
9B
Check if the slave is in power failure mode
YES/NO
x
A0
Returns the current light level as
XX
XX
x
Returns value from window side
A1
Returns the maximum allowed light level as
XX
XX
x
A2
Returns the minimum allowed light level as
XX
XX
x
A3
Return the power up level as
XX
XX
x
Will be 254, no meaning
A4
Returns the system failure level as
XX
XX
x
A5
Returns the fade time as
X
and the fade rate
as
Y XY
x
B0+
Scene Returns the light level
XX
for the
selected scene
XX
x
C0
Returns a bit pattern
XX
indicating which
group (0-7) the slave belongs to
XX
x
C1
Returns a bit pattern
XX
indicating which
group (8-15) the slave belongs to
XX
x
OSD
LRM2090 DALI commands
Executed for all OSD slave luminaires the same
Executed
Hex #
Command
Other