and the PAN08 not in overload status , it will send Alarm_Report, Alarm Type = 0x08, 

Alarm Level=0x00.

6-3.1 Alarm Report

When in Two Push Button switch type, S1 or S2 close to L and not been release, and

PAN08 receive some control moving command from Z-Wave RF (Ex. BASIC_SET

 

BINARY_SWITCH_SET

 

MULTILEVEL_SWITCH_SET

MULTILEVEL_SWITCH_START_LEVEL_CHANGE or

MULTILEVEL_SWITCH_STOP_LEVEL_CHANGE or SCENE_ACTIVATION_SET), 

PAN08 won’t do any change in position but report alarm to Group1 this indicate that 

the S1 or S2 not been released.

When PAN08 detect a overload power, it will report alarm to Group1  

[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm Level = 0xFF 

(Overload)]

[Command_Class_Alarm,  Alarm_Report,  Alarm   Type   =   0x08,  Alarm   Level   =   0x00

(Normal)] 

When in Two Push Button switch type, S1 or S2 are closed and not released to open,

and PAN08 receive any control moving command from Z-Wave RF, it will report 

alarm to Group1.

[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0xFF

 (S1 or S2 close to L)]

[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0x00

 (S1 and S2 released from L)]

7

Z-Wave’s Configuration

Configuration

Parameter

Function

Size

(Byte)

Value

Unit

Default Description

1

Watt 

Meter 

Report  

Period

2

0x01-

0x7FFF

5s

720

5*720s=3600s=1

hour

2

KWH 

Meter 

Report  

Period

2

0x01-

0x7FFF

10

min

6

6*10min= 1 hour

3

Threshold

of current

for Load 

Caution

2

10-500

0.01
A

500

500*0.01A=5A

4

Threshold

of KWH 

for Load 

Caution

2

1-

10000

1

KWh

10000

5

External 

switch 

1

1-2

2

1: 

One Push button

2:

Two Push button

10

Summary of Contents for PAN08-1A

Page 1: ...er Shutter This in wall Roller Shutter Controller is able to detect position of the Shutter by using the patterned power measuring method so it can be remote controlled not only fully up or down but also can be adjusted to ex 30 or 50 And when manual controlled by push button the controller also can memorize the position and send the new shutter position to its controller ex IP Gateway Adding to Z...

Page 2: ...ontroller into exclusion mode by following the instructions provided by the controller manufacturer One press one flash LED 2 Pressing Include button three times within 2 seconds will enter exclusion mode Node ID has been excluded LED 0 5s On 0 5s Off En ter auto inclusion Reset 1 Pressing Include button three times within 2 seconds will enter inclusion mode Use this procedure only in the event th...

Page 3: ...n learning mode LED flashes on and off alternately and repeatedly at 0 5 second intervals Overload When overload state occurs the PAN08 is disabled and LED flashes on and off alternately at 0 2 second intervals PAN08 will send alarm_type 8 alarm_Level 0xFF to Group1 Overload state can be cleared by disconnect and reconnect the PAN08 to the main power Choosing a Suitable Location 1 Do not locate th...

Page 4: ...ter simply press the external switch S1 or S2 The detail is described in 7 5 8 PAN08 built in meter function and can read the Watt KWh V Voltage I Current PF Power Factor of the load by using Z Wave command class user can set a threshold current to get the warning caused by abnormal operation 9 PAN08 have overload protection function and can help to prevent short circuit caused by load Programming...

Page 5: ... Command Command Class Binary Switch Binary Switch Get Binary Switch Report Command Command Class Binary Switch Binary Switch Report Value 0x00 BOT TOM Command Class Binary Switch Binary Switch Report Value 0xFE UN KNOWN Command Class Binary Switch Binary Switch Report Value 0xFF TOP 2 2 BINARY_SWITCH_SET PAN08 can only accept Binary Switch Set Command which value is either 0x00 Bottom or Top 0xFF...

Page 6: ...Command Command Class Multilevel Switch Multilevel Switch Report Value 0x00 BOTTOM Command Class Multilevel Switch Multilevel Switch Report Value 0x01 0x62 Between BOTTOM and TOP Command Class Multilevel Switch Multilevel Switch Report Value 0x63 0xFF TOP 3 3 MULTILEVEL SWITCH START LEVEL CHANGE This is the command which user can move the shutter up to the top or down to the bottom Command Class M...

Page 7: ...de bit 0 Level 0 99 or 255 The current setting of PAN08 will not be override Command Class Scene Actuator Configuration Scene Actuator Configuration Set Scene ID 1 255 Override bit 1 Level 0 99 or 255 The Level value in this Command is associated to the Scene ID 5 2 Scene Actuator Configuration Get Command Command Class Scene Actuator Configuration Scene Actuator Configuration Get Scene ID 1 255 C...

Page 8: ...Example Meter Value 1 0x00 W Meter Value 2 0x00 W Meter Value 3 0x03 W Meter Value 4 0xEA W Meter W Meter Value 3 256 Meter Value 4 100 2W 6 2 2 Accumulated Power Consumption KW h When receiving Meter Get Command it will report Meter Report Command to the node asked Meter Get Command Command Class Meter Meter Get Scale 0x00 KW h Meter Report Command Command Class Meter Meter Report Rate Type 0x01 ...

Page 9: ...current Meter Value 1 256 Meter Value 2 2 89 A 6 2 5 load power factor PF When receiving Meter Get Command it will report Meter Report Command to the node asked Meter Get Command Command Class Meter Meter Get Scale 0x06 PF Meter Report Command Command Class Meter Meter Report Rate Type 0x01 Meter Type 0x01 Precision 2 Scale 0x06 Size 1 Bytes Meter Value PF Example Scale 0x06 PF Precision 2 Size 1 ...

Page 10: ...erload Command_Class_Alarm Alarm_Report Alarm Type 0x08 Alarm Level 0x00 Normal When in Two Push Button switch type S1 or S2 are closed and not released to open and PAN08 receive any control moving command from Z Wave RF it will report alarm to Group1 Command_Class_Alarm Alarm_Report Alarm Type 0x01 Alarm Level 0xFF S1 or S2 close to L Command_Class_Alarm Alarm_Report Alarm Type 0x01 Alarm Level 0...

Page 11: ...lue is 1KWh and default value is 10000 kWh 7 5 External switch type 7 5 1 One Push Button When the configuration setting is One Push Button only S1 input will be valid The control moving commands can be accepted in this switch type while the shutter is moving In this switch type the inclusion exclusion reset association function can also be fulfilled by pressing S1 just like the operation of inclu...

Page 12: ... S2 7 6 Level Report mode Mode 1 In 5 seconds period after controlled by a moving command it will report the destination level when received request command Out of the 5 seconds period it will report the actual level of the shutter when received request command Mode 2 Whenever the shutter move pass a 10 percent level it will auto report the level to Group 1 node 8 Command Classes The Switch suppor...

Page 13: ... this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can take this...

Page 14: ... connected Consult the dealer or an experienced radio TV technician for help This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation FCC Caution Any changes or modifications not expressly a...

Reviews: