and the PAN08 not in overload status , it will send Alarm_Report, Alarm Type = 0x08,
Alarm Level=0x00.
6-3.1 Alarm Report
:
When in Two Push Button switch type, S1 or S2 close to L and not been release, and
PAN08 receive some control moving command from Z-Wave RF (Ex. BASIC_SET
、
BINARY_SWITCH_SET
、
MULTILEVEL_SWITCH_SET
、
MULTILEVEL_SWITCH_START_LEVEL_CHANGE or
MULTILEVEL_SWITCH_STOP_LEVEL_CHANGE or SCENE_ACTIVATION_SET),
PAN08 won’t do any change in position but report alarm to Group1 this indicate that
the S1 or S2 not been released.
When PAN08 detect a overload power, it will report alarm to Group1
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm Level = 0xFF
(Overload)]
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm Level = 0x00
(Normal)]
When in Two Push Button switch type, S1 or S2 are closed and not released to open,
and PAN08 receive any control moving command from Z-Wave RF, it will report
alarm to Group1.
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0xFF
(S1 or S2 close to L)]
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0x00
(S1 and S2 released from L)]
7
Z-Wave’s Configuration
Configuration
Parameter
Function
Size
(Byte)
Value
Unit
Default Description
1
Watt
Meter
Report
Period
2
0x01-
0x7FFF
5s
720
5*720s=3600s=1
hour
2
KWH
Meter
Report
Period
2
0x01-
0x7FFF
10
min
6
6*10min= 1 hour
3
Threshold
of current
for Load
Caution
2
10-500
0.01
A
500
500*0.01A=5A
4
Threshold
of KWH
for Load
Caution
2
1-
10000
1
KWh
10000
5
External
switch
1
1-2
2
1:
One Push button
2:
Two Push button
10