2-2-6 load power factor (PF)

 

        When receiving Meter Get Command, it will report Meter Report Command to the 
node.

 

 

Meter Get Command:

 [Command Class Meter, Meter Get, Scale =0x06(PF)]

 

Meter Report Command:

 

[Command Class Meter

Meter Report

Rate Type = 0x01

Meter Type = 0x01

 

Precision = 2

Scale = 0x06

Size = 1 Bytes

Meter Value(PF)]

 

 

Example:

 

Scale = 0x06 (PF)

 

Precision = 2

 

Size = 1 (1 Byte of    PF)

 

Meter Value 1 =    0x63(PF)    (It means that the load power factor is 0.99)

 

 

3.    Z-Wave’s Configuration

 

 

Configuration

 

Parameter

 

Function

 

Size

 

(Byte)

 

Value

 

Unit

 

Default

 

Description

 

1

 

Watt Meter 

Report Period

 

2

 

0x00-

 

0x7FFF

 

5s

 

720

 

0: Disable Watt Report

 

1~32767 : 5s~ 45h

 

2

 

KWH Meter 

Report Period

 

2

 

0x00-

 

0x7FFF

 

10min

 

6

 

0:Disable KWh Report

 

1~32767 : 10min~ 

227days

 

3

 

Threshold of

 

current for Load

 

caution

 

2

 

10-1300

 

0.01A

 

1300

 

1300*0.01A = 13A

 

4

 

Threshold of

 

KWh for Load

 

caution

 

2

 

1-10000

 

1KWh

 

10000

 

10000*1KWh  =  10000 

KWh

 

5

 

Restore switch 
state mode

 

1

 

0-2

 

 
 

1

 

0 : Switch off

 

1 : Last switch state

 

2 : Switch on

 

6

 

Mode of Switch 
Off function

 

1

 

0-1

 

 

1

 

0 : Disable

 

1 : Enable

 

7

 

LED indication 
mode

 

1

 

1-3

 

 

1

 

1 : Show switch state

 

2 : Show night mode

 

3 : One flash mode

 

8

 

Auto off timer

 

2

 

0-0x7FFF

 

1s

 

0

 

0 : Disable auto off 

function

 

1-0x7FFF : 1s ~ 

32767s

 

9

 

RF off 
command mode

 

1

 

0-3

 

 

0

 

0 : Switch off

 

1 : Ignore

 

2 : Switch toggle

 

3 : Switch on

 

11

 

Manual Switch 
Report mode

 

1

 

0-1

 

 

1

 

0 : Disable

 

1 : Enable

 

12

 

Auto Report 
after Reset

 

1

 

0-1

 

 

0

 

0 : Disable

 

1 : Enable

 

13

 

Adjustable 
Overload

 

2

 

450-1450

 

0.01A

 

1450

 

1450*0.01A=14.5A

 

 

3-1

 Watt 

Meter Report Period:

 

      If the setting is configured for 1hour (set value =720), PAN16 will report its instant 

power consumption to Group1 node every 1 hour. The maximum interval to report 
its  instant  power  consumption  is  45  hours  (5s*32767/3600=45hr).  When  the 
setting is 0, PAN16 will disable Watt auto report function. The default value is 720.

 

3-2 KWH Meter Report Period:

 

      If  the  setting  is  configured  for  1hour  (set  value  =6),  PAN16  will  report  its 

Accumulated  Power  Consumption  (KWh)  to  Group1  node  every  1  hour.  The 
maximum interval to report its Accumulated Power Consumption (KWh) is 227.55 
days (10min*32767/1440=227.55 days). When the setting is 0, PAN16 will disable 
KWH auto report function. The default value is 6.

 

3-3 Threshold of current for Load Caution

 

This is a warning when the current of load over the preset threshold value, if the

 

setting value is 1300, when the load current of Relay1 over this value, PAN16

 

will send current meter report to warn the Group1 node, the range of the setting

 

value is from 10 to 1300,and the default value is 1300.

 

3-4 Threshold of KWh for Load Caution

 

This is a warning when the KWh of load over the preset threshold value, If the

 

setting value is 10000, when the Accumulated Power Consumption of Relay1 over 

 

this value, PAN16 will send KWH meter report to warn the Group1 node,

 

minimum value is 1KWh and default value is 10000 kWh.

 

3-5 Restore switch state mode :

 

  Whenever the AC power return from lost, PAN16 will restore the switch state which 

could be SWITCH OFF

LAST SWITCH STATE

SWITCH ON. The default setting 

is LAST SWITCH STATE.

 

3-6 Mode of switch off function :

 

Summary of Contents for PAN16

Page 1: ...Off button with LED indicator which is used to toggle switch on and off or carry out inclusion exclusion reset or association When first power is applied its LED flashes on and off alternately and repeatedly at 0 5 second intervals It implies that it has not been assigned a node ID and start auto inclusion Auto Inclusion The function of auto inclusion will be executed as long as the switch does no...

Page 2: ...ternately at 2 second intervals By pressing On Off button it will stop flashing temporarily Learning When PAN16 is in learning mode LED flashes on and off alternately and repeatedly at 0 5 second intervals Overload When overload state occurs the Switch is disabled of which LED flashes on and off alternately at 0 2 second intervals Overload state can be cleared by unplugging and reconnecting the Sw...

Page 3: ...e Switch will report its latest status to Z Wave Controller Grouping 1 includes SWITCH_BINARY_REPORT METER_REPORT ALARM_REPORT 2 1 Auto report to Grouping 1 Maximum Node 1 2 1 1 On Off Event Report When on or off state has been changed it will send Binary Switch Report to the node of Grouping 1 Binary Switch Report ON Command Class Switch Binary Switch Binary Report Value 255 0xFF OFF Command Clas...

Page 4: ...learing accumulated power consumption Whenever re start counting the accumulated power consumption is needed you can use Meter Reset Command to clear it Meter Reset Command Command Class Meter Meter Reset 2 2 4 AC load Voltage V When receiving Meter Get Command it will report Meter Report Command to the node Meter Get Command Command Class Meter Meter Get Scale 0x04 V Meter Report Command Command ...

Page 5: ... 0 01A 14 5A 3 1 Watt Meter Report Period If the setting is configured for 1hour set value 720 PAN16 will report its instant power consumption to Group1 node every 1 hour The maximum interval to report its instant power consumption is 45 hours 5s 32767 3600 45hr When the setting is 0 PAN16 will disable Watt auto report function The default value is 720 3 2 KWH Meter Report Period If the setting is...

Page 6: ...enever PAN16 is repowered it will check this parameter for if sending a BINARY_SWITCH_ REPORT to the node of group1 or not The default setting is Disable the function 3 12 Adjustable Overload The overload current can be adjustable from 4 5A to 14 5A The default value is 1450 for 14 5A 1450 0 01A 14 5A 4 Protection Command Classes PAN16 supports Protection Command Class version 2 it can protect the...

Page 7: ...1 France type PAN16 2 UK type PAN16 3 Switzerland type PAN16 4 Note Please make sure that the intensity of the plug of the electrical device must be 16A and have same head as the enclosed plug before inserting to the socket ...

Page 8: ...oad occurs Remove the load attached or check max load cannot exceed 13A Resistive load Specification Operating Voltage 220V 240V 50Hz for EU Type Operating Voltage 100V 120V 50Hz 60Hz for US Type Maximum Load Ampere 13A Resistive load PAN16 1 PAN16 2 PAN16 3 Maximum Load Ampere 10A Resistive load PAN16 4 Switzerland Socket Type Germany type PAN16 1 France type PAN16 2 UK type PAN16 3 Switzerland t...

Page 9: ...ccordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the follow...

Reviews: