Displaying and adjusting parameters 

Switch position 

Function 

 

‘

 

Displays the ambient temperature 

 

‘

 

Allows you to view and adjust the temperature set point 

‘

 

Clears alarms 

 

‘

 

Allows you to view and adjust the differential (

di

), off set-back (

oS

), and idle 

speed (

id

). Each time the switch is clicked and then held in this position, the 

next parameter is displayed. The display flashes between the parameter code 
(two letters) and it's setting (two digits). You can adjust the parameter at this 
point. The cycle starts over after the last parameter. To restart at the beginning 
of the cycle, click the switch to the right. 

 

Parameter 

Code 

Range 

Factory setting  Location 

Temperature set point  

N/A 

32 to 99°F (0 to 38°C) 

N/A 

External knob 

Idle speed 

id 

0 - 99% 

N/A 

External knob 

Temperature differential  

di 

1 to 20°F (0.6 to 12°C) 

6°F 

Internal trimmer 

Off set-back 

oS 

0 to 16°F (0 to 9°C) 

5°F 

Internal trimmer 

°F or °C (ambient temp.) 

°

F

 / °

C

 

-22 to 99°F (-30 to 38°C) 

°F 

Internal jumper 

 

 

About hysteresis 

The VTC-1D has a 1°F (0.5°C) hysteresis. This means the fan will turn off 1°F below the temperature at 
which it turned on.  

For example, if temperature set point is 75°F, the fan turns on at 75°F, off at 74°F. This prevents the fan 
from flickering on and off when the temperature is at the set point. 

 

Setting the off set-back and selecting the mode of operation 

Auto shut-off (OSB) mode 

In auto shut-off mode, also called OSB mode, the fan shuts off when the temperature is below the off set-
back temperature. For more information, see 

Example 1: shut-off (OSB) mode

 on page 9. 

 

Idle mode 

In idle mode, the fan runs at the idle speed when the temperature is below the temperature set point. For 
more information, see 

Example 2: idle mode

 on page 10. 

 

Summary of Contents for VTC-1D

Page 1: ...idle mode Adjustable temperature set point Adjustable temperature differential Three second full power turn on to minimize fan ice up Two digit LED display Fahrenheit and Celsius display Error code di...

Page 2: ...the enclosure Use watertight strain reliefs or conduit connectors at all cable entry points Before removing electrical knockouts remove the cover to prevent damaging the control Do not make additiona...

Page 3: ...idelines and the guidelines below when extending cables Use two wire 18 AWG jacketed cable Phason recommends Belden 9408 Alpha 5052 or an equivalent Extension cable is also available from Phason For m...

Page 4: ...ower system is 60Hz 4 The display flashes between the temperature display and PF The pf indicates a power interruption has occurred To clear the PF click the switch to the right The control is now in...

Page 5: ...99 N A External knob Temperature differential di 1 to 20 F 0 6 to 12 C 6 F Internal trimmer Off set back oS 0 to 16 F 0 to 9 C 5 F Internal trimmer F or C ambient temp F C 22 to 99 F 30 to 38 C F Int...

Page 6: ...b to the desired setting while holding the switch to the right The temperature set point can be between 32 and 98 F 0 and 38 C 3 Release the switch You must hold the switch to the right while turning...

Page 7: ...factor calculate the correction as follows 1 Set the idle speed properly For more information see Setting minimum ventilation in idle mode on page 8 2 Set the differential to 10 F with the internal tr...

Page 8: ...g the voltage If you are unsure see your fan dealer for the minimum idle voltage for your fan motor 8 Press and hold the switch to the right 9 Turn the Temperature knob to the desired temperature set...

Page 9: ...ture set point When the temperature is between 80 F and 86 F the differential temperature fan speed changes proportionally with the temperature If the temperature increases fan speed increases If the...

Page 10: ...mperature fan speed changes proportionally with the temperature If the temperature increases fan speed increases If the temperature decreases fan speed decreases When the temperature is at or above 86...

Page 11: ...t that is labelled as non corrosive electronics grade or neutral cure such as GE Silicone RTV6780B RTV 142 or RTV 162 Do not use a sealant that is labelled as acetic acid cure or acetoxy cure These se...

Page 12: ...rovide proof of purchase upon request All transportation charges for products submitted for warranty must be paid by the purchaser Except to the extent prohibited by applicable law no other warranties...

Reviews: