Phason
VTC-1D user manual
11140010
3
Wiring the VTC-1D
1.
Set the voltage switch
A
to the correct position for
the line voltage used.
2.
Set jumper
E
to the correct position for the
temperature units (Fahrenheit or Celsius) you want
to use.
3.
Connect the incoming power and load wires as
shown in the diagram.
Connecting the temperature probe
Follow the guidelines below and connect the
temperature probe as shown in the diagram.
Do not run the probe cable in the same conduit as
AC power cables
Do not run the sensor cable beside AC power
cables or near electrical equipment.
When crossing other cables or power lines, cross
them at a 90 degree angle.
Using four-zone averaging
The VTC-1D can monitor the temperature in four
different zones. The control takes an average of the four
temperatures and operates according to the average
temperature.
To use four-zone averaging, you must connect four
temperature sensors to the unit. Connect the probes as
shown to the right.
Extending probe cables
You can extend temperature probe cables to lengths of up to 500 feet. Follow the temperature probe
guidelines and the guidelines below when extending cables.
Use two-wire 18 AWG jacketed cable. Phason recommends Belden # 9408, Alpha # 5052, or an
equivalent. Extension cable is also available from Phason. For more information, contact your dealer or
Phason.
If the unit operates erratically with the extended probe, run the cable along a different path or shorten it.
Service
box
Enclosure
I
H
F
A
Probe
Insulate
using a
#31 wire
nut or
similar
connector
Line/L1
Neutral/L2
Black
A
Fuse: 15 A, 250 VAC ceramic
B
Important:
A suitable switch must be installed between the control
and the motor.
Important:
Il est essentiel qu’un interrupteur convenable soit installé
entre le contrôle et le moteur.
C
Caution:
For controlling shaded-pole, permanent-split-capacitor, or
universal motors only.
Caution:
Destiné uniquement à la commande de moteurs universels.
À bague de déphasage ou à condensateur permanent.
D
Connect all ground wires to the grounding terminal located near the
cable entry points.
E
11150502
Use liquid-tight connectors at the cable entry points and seal with an
RTV silicone.
C
Before connecting the power, set
the switch to the correct setting
230 VAC
115
230
F
G
Temperature
differential set
White
Blue
20°F
1°F
115 VAC
G
B
D
E
Fan
Off set-back/idle
set mode
16°F
1°F
idle mode
I
H
Fahrenheit
Celsius