VTC-1D user manual 

11140010  

 

Wiring the VTC-1D 

1.

 

Set the voltage switch 

to the correct position for 

the line voltage used. 

2.

 

Set jumper 

E

 to the correct position for the 

temperature units (Fahrenheit or Celsius) you want 
to use.  

3.

 

Connect the incoming power and load wires as 
shown in the diagram. 

 

Connecting the temperature probe  

Follow the guidelines below and connect the 
temperature probe as shown in the diagram.  

‹

 

Do not run the probe cable in the same conduit as 
AC power cables  

‹

 

Do not run the sensor cable beside AC power 
cables or near electrical equipment. 

‹

 

When crossing other cables or power lines, cross 
them at a 90 degree angle. 

 

Using four-zone averaging 

The VTC-1D can monitor the temperature in four 
different zones. The control takes an average of the four 
temperatures and operates according to the average 
temperature.  

To use four-zone averaging, you must connect four 
temperature sensors to the unit. Connect the probes as 
shown to the right. 

 

Extending probe cables 

You can extend temperature probe cables to lengths of up to 500 feet. Follow the temperature probe 
guidelines and the guidelines below when extending cables. 

‹

 

Use two-wire 18 AWG jacketed cable. Phason recommends Belden # 9408, Alpha # 5052, or an 
equivalent. Extension cable is also available from Phason. For more information, contact your dealer or 
Phason. 

‹

 

If the unit operates erratically with the extended probe, run the cable along a different path or shorten it. 

Service

box

Enclosure

I

A

Probe

Insulate 
using a 

#31 wire 
nut or 
similar 
connector

Line/L1 

Neutral/L2 

Black

A

Fuse: 15 A, 250 VAC ceramic

B

Important:

A suitable switch must be installed between the control 

and the motor.  

Important:

 Il est essentiel qu’un interrupteur convenable soit installé 

entre le contrôle et le moteur.

C

Caution:

For controlling shaded-pole, permanent-split-capacitor, or 

universal motors only. 

Caution:

 Destiné uniquement à la commande de moteurs universels. 

À bague de déphasage ou à condensateur permanent. 

Connect all ground wires to the grounding terminal located near the 
cable entry points. 

E

11150502

Use liquid-tight connectors at the cable entry points and seal with an 
RTV silicone. 

C

Before connecting the power, set 

the switch to the correct setting 

230 VAC 

115 

230 

F

G

Temperature 
differential set 

White

Blue

20°F

1°F

115 VAC

B

D

E

Fan 

Off set-back/idle 
set mode 

16°F 

1°F 

idle mode 

I

H

Fahrenheit

Celsius 

Summary of Contents for VTC-1D

Page 1: ...idle mode Adjustable temperature set point Adjustable temperature differential Three second full power turn on to minimize fan ice up Two digit LED display Fahrenheit and Celsius display Error code di...

Page 2: ...the enclosure Use watertight strain reliefs or conduit connectors at all cable entry points Before removing electrical knockouts remove the cover to prevent damaging the control Do not make additiona...

Page 3: ...idelines and the guidelines below when extending cables Use two wire 18 AWG jacketed cable Phason recommends Belden 9408 Alpha 5052 or an equivalent Extension cable is also available from Phason For m...

Page 4: ...ower system is 60Hz 4 The display flashes between the temperature display and PF The pf indicates a power interruption has occurred To clear the PF click the switch to the right The control is now in...

Page 5: ...99 N A External knob Temperature differential di 1 to 20 F 0 6 to 12 C 6 F Internal trimmer Off set back oS 0 to 16 F 0 to 9 C 5 F Internal trimmer F or C ambient temp F C 22 to 99 F 30 to 38 C F Int...

Page 6: ...b to the desired setting while holding the switch to the right The temperature set point can be between 32 and 98 F 0 and 38 C 3 Release the switch You must hold the switch to the right while turning...

Page 7: ...factor calculate the correction as follows 1 Set the idle speed properly For more information see Setting minimum ventilation in idle mode on page 8 2 Set the differential to 10 F with the internal tr...

Page 8: ...g the voltage If you are unsure see your fan dealer for the minimum idle voltage for your fan motor 8 Press and hold the switch to the right 9 Turn the Temperature knob to the desired temperature set...

Page 9: ...ture set point When the temperature is between 80 F and 86 F the differential temperature fan speed changes proportionally with the temperature If the temperature increases fan speed increases If the...

Page 10: ...mperature fan speed changes proportionally with the temperature If the temperature increases fan speed increases If the temperature decreases fan speed decreases When the temperature is at or above 86...

Page 11: ...t that is labelled as non corrosive electronics grade or neutral cure such as GE Silicone RTV6780B RTV 142 or RTV 162 Do not use a sealant that is labelled as acetic acid cure or acetoxy cure These se...

Page 12: ...rovide proof of purchase upon request All transportation charges for products submitted for warranty must be paid by the purchaser Except to the extent prohibited by applicable law no other warranties...

Reviews: