At 10:30 AM, temperature compensation starts because the outdoor temperature plus the compensation
offset is higher than the high temperature alarm setting.
At 2:00 PM, there is an alarm condition because the zone temperature exceeds the high alarm maximum.
4:30 PM, there is an alarm condition because the room temperature exceeds the compensated high
alarm.
5:45 PM, compensation ends because the outdoor temperature plus the compensation offset is less than
the high temperature alarm setting.
on page 91 when programming alarms. The worksheet
contains descriptions of each setting.