10
VBMS ....
11. Technical data
11.1 Environmental conditions
Note:
Please pay attention and consider for the operation of IE3 motors while
dimensioning of combined motor start and braking devices the resulting
higher starting and braking currents.
For the use of IE3 motors we highly recommend to dimension and design
the needed combined motor start and braking devices one size higher.
Type designation VBMS
400-2,2/20
230-1,5/20
Ratetd operational voltage 50/60Hz
according to DIN EN 50160 (IEC 38)
3x 380/415V
±10%
3x 200/240V
±
10%
AC-3 Rated operational power
2.2kW
1.5kW
AC-3 Rated operational power on IE3 Motor
1.5kW
1.1kW
Conventional Thermal current I
th
= I
e
16A
Braking current
2...20A
max. braking time
10s
max. braking frequency at
braking current 10A
braking current 20A
at 5s braking time: 1 in 25s
at 10s braking time: 1 in 50s
at 5s braking time: 1 in 60s
at 10s braking time: 1 in 120s
Delay time during switch-off and braking
500ms
Braking voltage
0...220V DC
0...110V DC
max. Cross-sectional area
2.5mm² per terminal
Weightt
0.6kg
Storage temperature
-25 ... 75°C
Operating temperature
0 ... 45°C
Degree of protection
IP 20
Environment
Overvoltage category III, pollution degree 2