6.7 Clean Condenser Coil
ELECTROCUTION HAZARD!! Never attempt
to repair or perform maintenance on the
unit until the Main electrical power has
been disconnected.
Perlick’s warranty does not cover cleaning of
condenser.
The condenser is located directly behind the front
grille. See Figure 6-4.
Condenser coils that are covered with dust and
debris restrict air flow. This results in high head
pressures and lower efficiency due to longer run
times.
Use soft brush and vacuum to clean coil every 90
days, or more often if conditions require.
6.8 Ambient Temperature
High ambient temperature and high humidity
conditions may result in performance issues and/or
refrigeration system failure.
The unit must be protected from precipitation.
Do not subject to direct solar load.
Under extreme temperature and/or relative
humidity conditions the front face, gasket and/or
glass door may show signs of condensation. When
temperature and/or relative humidity conditions
return to normal condensation will disappear.