Back Bar Operation Installation Manual
Return to
20
PROBLEM
CAUSE
SOLUTION
Dixell Control: LED
Controller display is
flashing “HA”. Maximum
temperature alarm.
(continued)
Power
Incorrectly wired harness and/or internal
wiring connections.
Verify wiring per wiring diagram,
. Reconnect wires if needed.
Fans
Evaporator fan is not running.
Refer to
Coils
Evaporator coil has iced over.
Remove ice per
Condensing coil is not clean.
Clean with soft brush and vacuum.
Fins are bent or damaged.
Straighten fins.
Probe
Probe is not connected to the control.
Reconnect probe per
Air Infiltration
Sealing compound does not form a
complete seal.
Refer to
Door gasket is damaged or out of place. Refer to
.
Condensate drain line/air trap is not
positioned properly.
Reposition in loop. See
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge per
This is a critically charged system,
recharging should only be done when
all other options have been
thoroughly checked.
Dixell Control: LED
Controller display is
flashing “LA”. Minimum
temperature alarm.
Internal compartment has exceeded the
low temperature alarm preset value for over
30 minutes.
Incorrect control settings.
Return to factory settings.
See
Probe failure.
Refer to
for resistance values.
Replace probe if needed. See
.
Control failure.
Refer to