41
18.
POSSIBLE FAULTS DESCRIPTION
Symptoms
Tips
There are no signs of
operation of device despite
connection to the network.
Check:
If line fuses are not blown, replace if necessary
If the wire connecting panel with the executive module is plugged
correctly and if module is not damaged.
Preset boiler temperature
on the display is different
from the required one.
Check:
If in this time the HUW container is not loaded and if preset
temperature is set above the preset boiler temperature. If so then the
difference in readings will disappear after heating the HUW container or
reduce the preset HUW temperature.
If time periods are activated
–
then deactivate time periods.
CH pump is not working.
Check:
If boiler exceeded temperature above parameter
CH activating temp.
–
wait or reduce value of this parameter.
If
HUW priority
is activated which blocks CH pump
–
deactivate priority
be setting
HUW pump mode
on
No priority,
If CH pump is damaged or blocked.
Fan does is not working.
Check if plug jumper is installed for the limiter of safety temperature
STB on terminals 1-2, (the jumper should only be installed only in case
when temperature limiter is not connected).
If producer of the boiler has equipped it with temperature limiter STB
with manual return to original position, it should be unlocked by
untwisting the cover and twisting the button according to
documentation of boiler producer,
Check the fan and replace it if necessary.
Additional feeder is not
working (module B).
Check if feeder wires are correctly connected to terminals,
Check if there is a jumper on terminals 1-2 of module B,
Check if feeder engine is not damaged,
In case when engine work can be heard and fuel is not provided check
the feeder with its user manual.
Fuel feeder is not working /
does not provide fuel
Check if feeder wires are correctly connected to terminals,
If temperature limiter STB is connected to terminals 1-2, then check if
the circuit is not cut off due to boiler overheating,
Check if feeder engine is not broken or damaged,
In case when engine work can be heard and fuel is not provided check
the feeder with its user manual.
Fuel is not burnt off
completely, there are not
burnt remnants in ashes.
Fuel burns with big amount
of smoke, burner fades
Check settings output modulation
in menu: Boiler settings
→
Output
modulation.
Temperature
is
not
measured correctly.
Check if there is a good thermo contact between the temperature
sensor and measured surface,
Check if sensor wire not goes too closely to network wire,
Check if sensor is connected to terminal,
Check if sensor is not broken
–
check with point 12.9.
In HUW mode = SUMMER
heaters are hot, boiler is
overheated.
Increase value of parameter
HUW operation extension
to cool off the
boiler.
HUW pump is not working,
even if HUW container is
loaded
Set the parameter
HUW operation extension = 0
Summary of Contents for KSR Beta Pelet 16
Page 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Page 20: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 26: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ...1 ...
Page 58: ...2 ...
Page 72: ...16 ...
Page 73: ...17 ...
Page 74: ...18 ...
Page 75: ...19 ...
Page 76: ...20 ...
Page 77: ......
Page 78: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 98: ......
Page 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Page 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Page 135: ...43 ...
Page 136: ......
Page 137: ...1 ...
Page 138: ......
Page 142: ......
Page 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Page 153: ...17 ...
Page 154: ......
Page 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Page 183: ......
Page 184: ......