38
15.
ALARMS DESCRIPTIONS
15.1
FUMES MAX. TEMP. EXCEEDING
The alarm occurs after exceeding the
maximum fumes temperature. Turns off the
fan. It aims to protect the fumes
temperature sensor from damage due to the
impact of temperature exceeding the
strength
of
the
sensor.
Once
the
temperature drops, the regulator resumes
normal operation.
15.2
BOILER MAX. TEMP. EXCEEDING
Protection against boiler overheating is done
in 2 steps. In the first step , after exceeding
Boiler cooling off temperature,
the controller
tries to reduce boiler temperature by
dropping excess of heat to the HUW
container and by opening mixer servomotors
(only when
mixer service = activated CH
). If
temperature measured by HUW sensor
exceeds value
Max. temp. of HUW
then HUW
pump is deactivated, what is done to protect
users against scalding. If boiler temperature
decreases, then the controller returns to
normal operation. If the temperature will still
increase (reaches 95 degrees C) then
constant alarm will be activated of boiler
overheating joined with sound signal.
The alarm can be deleted by pressing
„TOUCH and PLAY” button or activating and
deactivating power to the controller.
Attention: locating temperature
sensor outside water coat of burner
i.e. on exhaust pipe is not
beneficial, because it may cause
delay
in
detecting
boiler
overheating state!
15.3
BURNER MAX. TEMP. EXCEEDING
Alarm appears after exceeding burner
temperature above service parameter:
Service settings
→
Burner settings
→
Other
→
Max. burner temp.
If the burner temperature increases above
this value the controller will begin burning off
procedure.
Alarm is deleted automatically after burner
temperature decrease by 10
q
C.
Function which protects against
back fire does not work when The
controller has no electrical power.
The controller can not be used as
sole protection of boiler against
back fire. Additional protecting
automatics is to be used.
15.4
BOILER TEMP. SENSOR DAMAGE
Alarm appears by boiler sensor damage and
by exceeding measuring scope of this sensor.
When alarm appears the boiler is activated.
Deleting is done by pressing TOUCH and
PLAY button or by deactivating and
activating the controller. The sensor is to be
checked and replaced if necessary.
Checking the temperature sensor is
described in point 12.9
15.5
BURNER TEMP. SENSOR DAMAGE
Alarm appears when burner sensor is
damaged or by exceeding measuring scope
of this sensor. After alarm the boiler is burnt
off.
Deleting is done by pressing TOUCH and
PLAY button or by deactivating and
activating electrical power to the controller.
It is necessary to check the sensor and
replace it if necessary.
Checking temperature sensor is
described in point 12.9.
The controller can operate by
disconnected feeder temperature
sensor, after setting parameter
Max. burner temperature =0
However it is not recommended,
because it causes deactivation of
boiler protection function against
back-firing to fuel container.
15.6
COMMUNICATION LOSS
Controlling panel is connected to remaining
electronics by digital communication joint
RS485. In case of damage of this wire on the
screen
following
information
will
be
displayed:
Lack of communication
The controller does not deactivate regulation
and operates normally with previously
programmed parameters. In case of alarm
Summary of Contents for KSR Beta Pelet 16
Page 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Page 20: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 26: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ...1 ...
Page 58: ...2 ...
Page 72: ...16 ...
Page 73: ...17 ...
Page 74: ...18 ...
Page 75: ...19 ...
Page 76: ...20 ...
Page 77: ......
Page 78: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 98: ......
Page 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Page 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Page 135: ...43 ...
Page 136: ......
Page 137: ...1 ...
Page 138: ......
Page 142: ......
Page 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Page 153: ...17 ...
Page 154: ......
Page 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Page 183: ......
Page 184: ......