37
generated.
Max. flue gas temperature
Defines the maximum flue gas temperature. Should the value be
exceeded, the "maximum flue gas temperature exceeded" alarm is
generated.
Additional feeder operation time
Defines the additional feeder (bunker feeder) operation time. The feeder
is attached to the additional B module. After that time, the additional
feeder operation is stopped despite the fact that the fuel level sensor
contacts are open. The fuel level sensor contacts are located in the
additional B module.
Exhaust fan
Activates the operation of the exhaust fan.
Min. exhaust fan power
Minimum exhaust fan power in % selectable by the user. It is used only
to limit the available fan power range. It is not used for the fan control
algorithm and should be as low as possible to ensure slow and smooth
fan rotation and unrestricted flue gas extraction.
14.2
BOILER SERVICE SETTINGS
Thermostat selection
Options to choose from:
x
Deactivated (deactivates room thermostat influence on boiler
operation)
x
Universal (activates room thermostat for boiler)
x
ecoSTER T1 (option available after connecting room panel Room
Control TOUCH, boiler operation is dependent on room thermostat
No1 in Room Control)
x
ecoSTER T2 (option available after connecting room panel Room
Control TOUCH, boiler operation is dependent on room thermostan
No 2 in Room Control
–
on sensor CT7)
x
ecoSTER T3 (option available after connecting room panel Room
Control TOUCH, boiler operation is dependent on room thermostat
No3 in Room Control TOUCH
–
on sensor CT7)
Min. boiler temp.
Minimum preset boiler temperature which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Max. boiler temp.
Maximum preset boiler temperature which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Reserve boiler
Description in point 12.13
Alarm indication
Configuration of the alarm output so that it is activated if one or more
selected alarms occur.
Boiler cooling temperature
Temperature of boiler cooling off. Above this temperature the controller
activates HUW pump and opens mixer cycles to allow boiler cooling off.
The controller activates HUW pump if this temperature exceeds
maximum value. The controller will not open mixer cycle when
mixer
setting
=
floor active
Parameter A FuzzyLogic
Parameter B FuzzyLogic
Parameter C FuzzyLogic
Refer to FuzzyLogic mode. They have influence on quickness of
reaching boiler temperature to preset value and on stability of
maintaining this temperature. It is not recommended to change those
parameters if quickness of regulation and stability of maintaining preset
temperature is on expected level.
Pump off by thermostat
Options available
x
NO (CH boiler pump is not activated when room thermostat starts
operation),
x
YES (CH boiler pump is deactivated when room thermostat starts
operating)
Summary of Contents for KSR Beta Pelet 16
Page 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Page 20: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 26: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ...1 ...
Page 58: ...2 ...
Page 72: ...16 ...
Page 73: ...17 ...
Page 74: ...18 ...
Page 75: ...19 ...
Page 76: ...20 ...
Page 77: ......
Page 78: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 98: ......
Page 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Page 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Page 135: ...43 ...
Page 136: ......
Page 137: ...1 ...
Page 138: ......
Page 142: ......
Page 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Page 153: ...17 ...
Page 154: ......
Page 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Page 183: ......
Page 184: ......