![Pepperl+Fuchs VBG-ENXK20-D Manual Download Page 51](http://html1.mh-extra.com/html/pepperl-fuchs/vbg-enxk20-d/vbg-enxk20-d_manual_1527748051.webp)
AS-i 3.0 EtherNet/IP+Modbus TCP Gateway
EtherNet/IP interface
26
.9.20
1
3
51
10.6
AS-i slave Object
class code: 101 (0x65)
64 instances for each AS-i circuit, 1 for each AS-i slave
instance ID
AS-i slave
1 (0x01)
slave 0, circuit 1
2 (0x02)
slave 1A, circuit 1
…
…
32 (0x20)
slave 31A circuit 1
33 (0x21)
empty, circuit 1
34 (0x22)
slave 1B, circuit
…
…
64 (0x40)
slave 31B, circuit 1
65 (0x41)
slave 0, circuit 2
…
…
96 (0x60)
slave 31A, circuit 2
97 (0x61)
empty, circuit 2
…
…
98 (0x62)
slave 1B, circuit 2
…
…
128 (0x80)
slave 31B, circuit 2
Tab. 10-17.
attribute
ID
access
rule
name
devicenet
data type
remark
100 (0x64)
get
actual configuration
UINT
101 (0x65)
get/set
permanent configuration
UINT
slave 0, 32: not read-/writea-
ble
102 (0x66)
get/set
actual parameters
USINT
103 (0x67)
get/set
permanent parameters
USINT
104 (0x68)
get/set
xID1
USINT
slave 0: writeable only,
slave 0 - 32: readable
Tab. 10-18.
actual configuration/permanent configuration (16-bit)
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
ID
IO
xID2
XID1
Tab. 10-19.
parameter xID1 (8-bit)
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
–
data
Tab. 10-20.