Subject to reasonable modifications due to technical advances.
© Fuchs, Printed in Germany
15
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
Internet http://www.pepperl-fuchs.com
Iss
u
e d
a
te
: 17
.4
.20
09
AS-Interface
Spezifications
4.
Spezifications
4.1
Technical data
4.1.1
Data sheet VBG-EN-K30-DMD-S16
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.
VBG-EN-K30-DMD-S16
Ethernet/IP interface
RJ-45
Baud rates
10/100 MBaud
Serial interface
RS 232
AS-i cycle time
150
P
s
*
(number of 2)
Safety monitor
Release circuit
4-channel
Start delay
< 10 s
Respond delay
< 40 ms
Inputs:
4 x EDM/Start
EDM: inputs of external device monitoring circuits
start: start inputs
switching current statical 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs)
Output:
4 x output switching elements
relay outputs (output circuits 1 and 2)
max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V
semiconductor outputs (output circuits 3 and 4)
max. contact load: 0,5 A DC-13 at 30 V
Card slot
chip card for storage of configuration data
Displays
LCD
indication of slave addresses and error messages
LED power
power on
LED net
Ethernet/IP master recognized
LED config error
configuration error
LED U AS-i
AS-i voltage OK
LED AS-i active
AS-i normal operation active
LED prg enable
automatic addresses programming enabled
LED prj mode
configuration mode active
LED AUX
auxiliary power