Pulscon LTC
Function group "basic setup" (00)
D
O
C
T
-0
0
9
4
A
0
6
/2
009
12
07
82
13
3
Function group "basic setup" (00)
3.1
Function "measured value" (000)
This f
u
nction displays the c
u
rrent meas
u
red val
u
e in the selected
u
nit
(see
"customer unit" (042)
) f
u
nction). The n
u
m
b
er of digits after decimal point can
b
e
selected in the
"no.of decimals" (095)
f
u
nction.
3.2
Function "tank properties" (002)
This f
u
nction is
u
sed to select the tank properties.
Selection:
•
standard
•
al
u
mini
u
m tank
•
plastic tank
•
b
ypass/pipe
•
coax pro
b
e
•
concrete wall
standard
The
"standard"
option is recommended for normal containers for rod and rope pro
b
es.
aluminium tank
The
"aluminium tank"
option is designed especially for high al
u
mini
u
m silos that ca
u
se
an increased level of noise when empty. This option is only
u
sef
u
l for pro
b
es longer than
4 m. For short pro
b
es (< 4 m) select the
"standard"
option!
!
Note!
If
"aluminium tank"
is selected, the device cali
b
rates of its own accord when first filled,
depending on the medi
u
m's properties. Slope errors can, therefore, occ
u
r when
b
eginning the first filling proced
u
re.
plastic tank
Select the
"plastic tank"
option when installing pro
b
es in wood or plastic containers
without
metallic s
u
rfaces at the process connection (see installation in plastic
containers). When
u
sing a metallic s
u
rface at the process connection, the
"standard"
option is s
u
fficient!
!
Note!
In principle the employment of a metallic s
u
rface area sho
u
ld
b
e preferred at the
process connection!
E
+
–
E
+
–
E
+
–