Troubleshooting
9
Troubleshooting
9.1
Errors when programming outputs
If you experience difficulties when programming the outputs of the inductive position measuring
system, you will find below a list of the possible causes and information on troubleshooting.
Fault
Cause
Rectification
Sensor cannot be placed in
programming mode (LED
does not flash when button is
pressed)
Button not pressed long
enough
Press the button for program
-
ming the output
2 s.
Sensor cannot be placed in
programming mode (LED
does not flash when button is
pressed)
No target mounted
Mount the BT-F130-A target or
your own suitable target
Sensor cannot be placed in
programming mode (LED
does not flash when button is
pressed)
Customer's own target is
mounted too far away from
sensor surface
Mount a target according to
specification (see chapter 5.2)
LED stops flashing
Timeout when programming
the output.
Place sensor in programming
mode again
After programming, the
switching point or the start
point of the analog output is
still unchanged.
Programming process not
concluded within the time
-
frame
Conclude the programming
process by pressing the but
-
ton corresponding to the out
-
put a second time within the
timeframe (see chapter 6.1 or
see chapter 6.2)