LUC-M** with HART/4 mA ... 20 mA and PROFIBUS PA
Function group "output" (06) and "profibus param." (06)
D
O
C
T
-08
43A
01/
2010
1855
72
45
8.11
Function "simulation" (065)
If necessary, linearisation, the output signal and the current output can be tested with
the simulation function. You have the following simulation options:
Selection:
•
sim. off
•
sim. level
•
sim. volume
•
sim. current (HART only)
sim. off
Simulation is switched off.
sim. level
Enter the level value in
"simulation value" (066)
.
The functions:
•
"measured value" (000)
•
"measured level" (0A6)
•
"output current" (067) – only with HART instruments!
follow the entered values.
sim. volume
Enter the volume value in
"simulation value" (066)
.
The functions
•
"measured value" (000)
•
"output current" (067) – only with HART instruments!
follow the entered values.
sim. current (HART only)
Enter the current value in
"simulation value" (066)
.
The function
•
"output current" (067) – only with HART instruments!
follows the entered values.
E
+
–
sim. c
u
rrent
(HART only)
sim.
v
ol
u
me
sim. le
v
el
0 % ... 100 %
4 mA ... 20 mA
E
+
–
Summary of Contents for LUC-M Series
Page 69: ...LUC M with HART 4 mA 20 mA and PROFIBUS PA Notes DOCT 0843A 01 2010 185572 69...
Page 70: ...LUC M with HART 4 mA 20 mA and PROFIBUS PA Notes DOCT 0843A 01 2010 185572 70...
Page 71: ...LUC M with HART 4 mA 20 mA and PROFIBUS PA Notes DOCT 0843A 01 2010 185572 71...
Page 72: ...LUC M with HART 4 mA 20 mA and PROFIBUS PA Notes DOCT 0843A 01 2010 185572 72...
Page 74: ...LUC M with HART 4 mA 20 mA and PROFIBUS PA Notes DOCT 0843A 01 2010 185572 74...