Function group "safety settings" (01)
D
O
C
T
-08
43A
01/
2010
1855
72
22
hold
If the instrument is in alarm state, the last measured value is held.
user specific
If the instrument is in an alarm state, the output is set to the value configured in
"output on alarm"
(011)
(x mA).
"
Caution!
This selection is available for HART devices only!
4.2
Function "output on alarm" (011), HART only
The current (in mA) which will be output in case of an alarm. This function is active when
you selected
"user specific"
in the
"output on alarm" (010)
function.
"
Caution!
This function is available for HART devices only!
HART
t
t
PROFIBUS PA
Hold
Hold
3.6
-10 %
110 %
(110 %)
(-10 %)
[mA]
22
3.6
(-10
%
)
(110
%
)
E
+
–