LUC-M** with HART/4 mA ... 20 mA and PROFIBUS PA
Function group "basic setup" (00)
D
O
C
T
-08
43A
01/
2010
1855
72
18
3.9
Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured
distance must be compared with the actual distance to the product surface. The
following options are available for selection:
Selection:
•
distance = ok
•
dist. too small
•
dist. too big
•
dist. unknown
•
manual
distance = ok
•
Mapping is carried out up to the currently measured echo.
•
The range to be suppressed is suggested in the
"range of mapping" (052)
function.
Anyway, it is wise to carry out a mapping even in this case.
dist. too small
•
At the moment, an interference is being evaluated.
•
Therefore, a mapping is carried out including the presently measured echoes.
•
The range to be suppressed is suggested in the
"range of mapping" (052)
function.
dist. too big
•
This error cannot be remedied by interference echo mapping.
•
Check the application parameters
(002), (003), (004)
and
"empty calibr." (005)
.
E
+
–
distance too small