LUC-M** with HART/4 mA ... 20 mA and PROFIBUS PA
Function group "safety settings" (01)
D
O
C
T
-08
43A
01/
2010
1855
72
23
4.3
Function "outp. echo loss" (012)
Use this function to set the output response on echo loss.
Selection:
•
alarm
•
hold
•
ramp
%
/min
alarm
On echo loss, the instrument switches to alarm state after an adjustable
"delay time" (014)
. The output response depends on the configuration set in
"output on alarm"
(010)
.
hold
On echo loss, a warning is generated after a definable
"delay time"
(014)
. Output is
held.
ramp %/min
On echo loss, a warning is generated after a definable
"delay time"
(014)
. The output is
changed towards 0
%
or 100
%
depending on the slope defined in
"ramp %span/min"
(013)
.
E
+
–
delay time (014)
delay time (014)
delay time
(014)
ramp
%
span/min
(013)