11.4.6 DB 13: Out-address list
The OUT-address list contains the logical output addresses of the subscribers. The
list is an image of the Ident-Code list.
Each list position which is occupied by an output module is provided with an output
address. This forms the basis of the module in the control system.
In the example:
The analyser unit is assigned output words 30 - 36 in the control system.
List structure:
Legend:
DW 1
KY 000,030
IVI-4HB5
DW y
KY=
000,PC
Number of parameters
DW y+1
KY=
B,ADR
1st module
DW y+2
KY=
B,ADR
2nd module
..
.
..
.
..
.
..
.
DW y+n-2 KY=
B,ADR
nth module
DW y+n-1 KY=
B,ADR
Special ID-Code
DW y+n
KY=
B,ADR
Special ID-Code
PC =
Number of following parameters
B =
Address range
0 = P - range of the control system
1 = Q - range of the control system
ADR =
Base address of the module (0 - 255)
Word-oriented module = even address
Byte-oriented module = odd/even address
;OUT-address list
0:
KY 0,3
;number of parameters
1:
KY 0,30
;IVI- ... -4HB5
2:
KY 0,0
;diagnosis-bit register
3:
KY 0,0
;diagnosis-parameter register