![Pepperl+Fuchs IVI-KHA6-4HB5 Manual Download Page 43](http://html1.mh-extra.com/html/pepperl-fuchs/ivi-kha6-4hb5/ivi-kha6-4hb5_manual_1527940043.webp)
IDENT-I • IVI-KHD2-4HB5, IVI-KHA6-4HB5
Commissioning an S5 135U with INTERBUS-S interface
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com
D
a
te
of
is
su
e
3
0.
07
.2
0
0
1
41
11.4.5 DB 12: IN-address list
The IN-address list contains the logical input addresses of the subscribers. The list is
an image of the Ident-Code list.
Each list position which is occupied by an input module is provided with an input
address. This forms the basis of the module in the control system.
In the example:
The analyser unit is assigned input words 20 - 26 in the control system.
List structure:
Legend:
DB 12:
DW 1
KY 000,020
IVI-4HB5
DW y
KY=
000,PC Number of parameters
DW y+1
KY=
B,ADR
1st module
DW y+2
KY=
B,ADR
2nd module
...
...
...
...
DW y+n-2 KY=
B,ADR
nth module
DW y+n-1 KY=
B,ADR
Special ID-Code
DW y+n
KY=
B,ADR
Special ID-Code
PC =
Number of following parameters
B =
Address range
0 = P - range of the control system
1 = Q - range of the control system
ADR =
Base address of the module (0 - 255)
Word-oriented module = even address
Byte-oriented module = odd/even address
;IN-address list
0:
KY 0,3
;Number of parameters
1:
KY 0,20
;IVI- ... -4HB5
2:
KY 0,126
;diagnosis-bit register
3:
KY 0,128
;diagnosis-parameter register