5.4.2
Information for connecting the read/write head cable
The connecting cables to the read/write heads must be shielded. The cross section
of the cables must be at least 0.14 mm
2
.
The screen of the read/write head lead is connected on both sides to earth (PE) with
low resistence and low induction. For that the attached terminal block can be used
(see Figure 5.5).
Figure 5.5
Terminal block with connecting cables
Read/write head cable lengths up to 50 m or 100 m are possible if the following con-
ditions are satisfied.
up to 50 m
read/write head cable:
cross sectional area of at least 4 x 0.25 mm
2
maximum resistance 78 Ohm/km
maximum capacitance 90 pF/m
(e.g. LIYC11C, Mukkenhaut & Nusselt MUNFLEX
C11Y)
up to 100 m
read/write head cable:
cross sectional area of at least 4 x 0.5 mm
2
maximum resistance 37 Ohm/km
maximum capacitance 90 pF/m
With a cable length of 100 m, a series resistor of 82 Ohm must be fitted
in the cable connected to the 'Reset' terminal of the heads.
Since more EM interference can result with longer cable lengths, the
maximum cable lengths given above might not be possible for some
applications.