H D 2 - D M - A / D M - A M
Operation with the Diagnostic Manager
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
61
187630
7.
Press the button
Next
System warning and alarm limit values are now stored to the diag-
nostic device
•
Figure 8.3: Segment commissioning successful
8.2
Diagnostics
The Diagnostics functionality allows supervision of the whole produc-
tion plant with only one action to do. It displays all systems, segments
and field devices a alarm has occured at a glance. The last 500 alarms
of each Diagnostic Module are shown. The alarm data is collected with-
in a circular buffer.
You can launch the Diagnostic function separated for:
•
the whole production plant (System Diagnostic window) or
•
each single Diagnostic Module.
8.2.1
System Diagnostics Window
The System Diagnostic window shows all alarm status of each moni-
tored segment sorted by Diagnostic Module. Press "Open" to display
the Diagnostics window for the Diagnostic Module chosen.
#
Open System Diagnostics Window
1.
Right-click on the Fieldbus Diagnostic Server in the project tree
2.
Choose
Diagnostics
The System Diagnstics window appears.
If necessary modify the limit values before storing them to the Diagnostic
Module.
A Out of Specification alarm limit will be disabled, if the automatically cal-
culated maintenance alarm limit value violates the Out of Specification
limit. Expect the primary and secondary power supply alarms.