Stop ramp
t = XX [sec]
3
Slower ramps demand less stress on the motor and pump and
contribute towards extending their service life. On the other
hand, response times are longer.
Excessively fast start-up ramps can cause OVERVOLTAGE in
the E-IPFC.
Automatic start-up
ON/OFF
ON
By selecting ON, once the mains power has returned after a power
failure, the E-IPFC will resume operations in the same condition as
it was before the power failure. This means that if the pump was
running it will resume doing so.
Connectivity parameters
Parameter
Default
Description
MODBUS address
XXX
1
MODBUS address from 1 to 247
MODBUS baudrate
XXXXX
9600
MODBUS baudrate from 1200 bps to
57600 bps
MB data format
XXXXX
RTU N81
MODBUS data format: N81 RTU, N82
RTU, E81 RTU, O81 ETU
Should the default parameters be changed, confirm by sending the update to the machine by using the “WRITE”
button.
PI control
Stopping ramp
Control ramp
Min. mot. f. ramp
Min. mot. f. ramp
Min. motor freq.
Max. motor freq.
Min. control f.
Starting ramp
Stopping delay
47