Installation and User’s Guide
PRESS POOL/SPA TO
EXIT SETUP
8.
Input Screen
– The Input screen is a diagnostic display which shows the status of the input sensors. The
number 1 is displayed when the associated input is on and zero is displayed when the associated input is off.
WP
= Water Pump Switch
HP
= High Refrigerant Pressure Switch
LP
= Low Refrigerant Pressure Switch
PL
= Pool Remote
SP
= Spa Remote
9.
Output Screen
– The Output screen is a diagnostic display which shows the status of the Output devices.
The number 1 is displayed when the associated output is on and zero is displayed when the associated output
is off.
FAN
= Fan
COMP
= Compressor
PMP
= Pump
REV
= Reversing valve
10.
Exit
– Pressing the POOL/SPA button while this screen is displayed returns the display to the Pool or Spa Run
Screen as appropriate.
LOCKING THE CONTROL PANEL
1.
Heat pump control panel lock-out
– To prevent unwanted adjusting or manipulating of the heat pump
settings, the control panel can be locked. Once locked, if any button is pressed, the display will read:
•
To activate the control panel lockout, press the MENU SELECT and POOL/SPA buttons simultaneously.
•
To unlock the control panel, press the MENU SELECT and POOL/SPA buttons simultaneously.
DEFROST CYCLE
At air temperatures around 50° F, the heat pump may enter a defrost cycle. The defrost cycle is initiated when a
sensor on the evaporator detects that the refrigerant temperature has fallen below the defrost set point. At this
time, the heat pump compressor will stop. The heat pump evaporator fan will continue to run, and will draw air
over the evaporator fins for about 15 minutes. If, at the end of the 15 minutes, the temperature sensor detects a
temperature above 44° F, the compressor will restart. Otherwise the unit will shut down.
Because a heat pump's efficiency decreases as air temperature decreases, it is preferable to operate the heat
pump during the warmest time of day. As a rule, the unit should not be operated during the coolest time of day, or
when the air temperature falls below 45° F.
WP HP LP PL SP
1 1 1 0 0
FAN COMP PMP REV
1 1 1 0
HEAT PUMP
CONTROLS LOCKED