Fairbanks Nijhuis™
11/12/12
Intelliboost™ Water Booster System
Basic Operation Manual
6
Menu button is touched. When correct password/pin is entered, Menu screen will display. If incorrect, returns to
screen with message “Incorrect Password”. Reenter correct password/pin or ESC.
Factory Default Password/Pin: 999.
Bypass Password Protection. Basic and Advanced Passwords may be accessed from Home screen. Record Model
Number, Serial Number and call factory.
Drive Controls – VFD in Auto.
Realtime Drive information and Controls. Drive controls remote to HMI allow basic
drive operation without using the Local Control Panel at VFD. Drive screens monitor basic Drive Parameters, Speed
in Hz and VFD On/Off. VFD must be in Auto Mode for this screen operation. In case of transducer failure, Manual
Control will be switched to ON. Fault or Alarm will occur (Basic
Setup 4). Turn Drive ON to manually change speed. Drive Control
screens are created for each Drive in system.
Hardware Connections To Controller.
Select device that is
currently connected to Controller. This is a Factory Setting and
should never be adjusted without consulting factory.
Speed Max/Min Settings.
HMI Manual Max Speed – The max
speed that can be set on the Drive screens when HMI is used as
Manual Control operation for VFD. VFD must be in Auto On.
Max Speed VFDs
– Maximum speed VFD can operate when in
Auto On mode and Controller is in operation.