Fairbanks Nijhuis™
11/12/12
Intelliboost™ Water Booster System
Basic Operation Manual
3
NORMAL OPERATION (AUTO ON – VFD):
The Pump Controller receives a system pressure signal from the Discharge Pressure Transducer. The signal is
compared to the Setpoint and the pump(s) speed is adjusted.
Setpoint: Desired system pressure in psi.
INPUT TRANSDUCER SETTINGS: Discharge, Suction and Flow. Only Discharge or Flow is required
for operation.
CONTROLLER HMI AND SETTINGS:
HOME SCREEN.
Home screen shows real-time system
operation, status, settings and hardware. Alarms, Faults and
Maintenance indicators are active when called for and may be
accessed through this screen. Audio/Visual indication set to
Relay 1. May be enabled or disabled by touching
Horn & Lt,
R1
. Home screen is the default screen. Period of inactivity will
display a screensaver, if enabled by user.
No entries are accepted on the Home screen; it is an
information screen only.
MENU:
Menu is the base of navigation throughout the
program.
Menu may be Password Protected, if Enabled (refer to Basic
Setup 4).
Advanced Settings are used only when engineered changes
are required.
Password Protection Setup on Advanced Menu screen.
Default, Enabled Password/Pin – 999.
If Password Protection for Menu is activated, Password Entry
Basic screen will display when Menu button is touched. When
correct password/pin is entered, Menu screen will display. If
incorrect, returns to screen with message “Incorrect Password”.
Reenter correct Password/Pin or ESC.
Factory Setting – Disabled.