background image

Fairbanks Nijhuis™

11/12/12

Intelliboost™ Water Booster System

Basic Operation Manual

15

NOTICE: The suction pipe requires a check valve or isolation valve. 

  1.  Close to discharge isolation valve. 

NOTICE: Please see “Starting” before proceeding any further. 

CHECKING DIRECTION OF ROTATION

NOTICE: Do not disconnect the motor from the shaft to check the direction of rotation. If you remove the coupling, 

then you must adjust the shaft position when you reinstall it. This must be done before starting the pump. 

Danfoss Drive Preventive Maintenance Instruction 

PM Checklist

 

r

  Vacuum dust and dirt from heat sink fins 

 

r

  Clean or replace as conditions require intake air filters (125 Hp constant torque models, 150 Hp variable torque  

 

  models and larger have filters located behind the intake louver panels) 

 

r

  Check ventilation fans for proper operation and clean as needed. 

 

r

  Confirm VFD’s ventilation clearances have not been obstructed 

 

r

  Check electrical connections and re-torque as needed. If possible, perform an IR thermal scan of the VFD’s    

 

  power input and power output. 

 

r

  Check line voltage 

 

r

  Check motor & output phase balance 

 

r

  Inspect DC buss capacitors (older drives) 

 

r

  Record the VFD’s parameter settings using MCT-10 

 

r

  Confirm the VFD doors and covers are in place and properly closed 

2. Clean the drive’s interior. 

  a.  Dirt coating drive circuit boards and other components can interfere with proper cooling and even provide a path 

for electricity to short out along unintended paths. This can cause erratic operation and possibly damage to drive 

components. 

  b.  Corroded electrical connections can cause excess heat build-up, short circuits, erratic drive operation, and even 

component damage. 

  c.  This should be done after the installation of the drives is complete and before power is applied to the drive. The 

main point here is to ensure that no metal filings or other installation-related dirt are inside the drive or its option 

enclosure. 

  d.  If the drive is installed in an area where a lot of construction work will be performed, it is best to keep the drive 

covered while it is not in operation. Of course, if it is being used, the drive must be uncovered so that cooling air 

can be freely supplied to it. After the construction is complete it will be important to clean the interior of the drive. 

Low pressure, clean, dry air or similar commercial products can be used to clean dirt off of circuit boards. While 

a vacuum cleaner can be used to collect falling dirt, it is important to ensure that circuit boards are not damaged 

by the use of a powerful vacuum cleaner on the boards. Inspect drive connectors for dirt or corrosion. 

  e.  In a normal environment, the drive’s interior should be inspected annually and cleaned, if necessary. In dirty 

environments, more frequent inspection is required. The level of dirt found inside the drive can be used to dictate 

the frequency of inspections and cleanings that is required. 

3. Clean air filters (if any). 

  a.  Many VLT drives have no air filters. However, some sizes and enclosure styles do use air filters in conjunction 

with their fan cooling systems. For these drives it is important to periodically inspect and clean or replace the 

filter element. 

  b.  Because the loading of the air filters can vary dramatically from one installation to another, it is important to 

initially check the air filters frequently to establish the required inspection interval

Summary of Contents for FAIRBANKS NIJHUIS INTELLIBOOST 7710 Series

Page 1: ...sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system 7710 SERIES INTELLIBOOST WATER BOOSTER SYSTEM BASIC OPERATION MANUAL Part FM 03 554 201...

Page 2: ...of communication will stop drive after Timeout Each drive shares the same parameter set except where drive name is required Drive1 2 Drive2 3 Drive3 4 Drive4 5 A Master Local Control Panel LCP is used...

Page 3: ...Audio Visual indication set to Relay 1 May be enabled or disabled by touching Horn Lt R1 Home screen is the default screen Period of inactivity will display a screensaver if enabled by user No entrie...

Page 4: ...turned on Other pumps that follow are Lag pumps Lead pump will turn on when minimum PSI is not met and Lead pump Time Delay is timed out Staging on of the pumps once Lead pump is established is based...

Page 5: ...ne if flow is established Fault will stop all drives Password Setup Disabled Enable When password Enabled enter up to 4 numbers and record new password pin When enabled Password screen will display if...

Page 6: ...Control Panel at VFD Drive screens monitor basic Drive Parameters Speed in Hz and VFD On Off VFD must be in Auto Mode for this screen operation In case of transducer failure Manual Control will be swi...

Page 7: ...charge Alarms and Faults Alarms are set values to warn of conditions that may be harmful or undesirable for system Alarms Reset when system returns to desired operational values Alarm is recorded in N...

Page 8: ...led for continued operation EQUIPMENT MAINTENANCE ALARM BASED ON HOURS OF OPERATION AND STARTS Alarm set to be indicated on Home screen Disable Alarms enter 1 at default Maintenance indicator will als...

Page 9: ...larms is a set value not to be exceeded If exceeded within a set time period a Fault will occur and system will stop operating Fault restart requires Operator assistance Fault must be cleared or disab...

Page 10: ...40 VAC 50 60 Hz Operator Controls Power Off On Switch Operator Touch Screen 5 7 Color Touch Panel Audible Visual Alarm Control Connections RS485 communication port to VFDs Discharge Pressure Transduce...

Page 11: ...working on the pump Make sure that the power is locked out and that the pump cannot be accidentally started NOTICE Under no circumstances should the pump be operated without flow through the pump Nev...

Page 12: ...ing guard 3 Verify that the electrical connections are in accordance with the wiring diagram on the motor 4 If the fan is visible turn on and off to verify rotation 5 To reverse the direction of rotat...

Page 13: ...regreasing provisions Service Conditions NEMA Frame Size 140 180 210 360 400 510 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM Standard 3 years 6 mon...

Page 14: ...Low voltage at peak times 4 Motor starter has not tripped out but the motor does not run A Power failure B Fuses blown C Main contacts in motor starter are not making contact or the coil faulty D Con...

Page 15: ...ause excess heat build up short circuits erratic drive operation and even component damage c This should be done after the installation of the drives is complete and before power is applied to the dri...

Page 16: ...reapplied the fans should start and run for a few seconds d Listen for unusual noises from the fans when they are running e The VLT drives use a heat sink temperature sensor to help indicate if there...

Page 17: ...Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual 17 THIS PAGE LEFT BLANK INTENTIONALLY...

Page 18: ...Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual 18 THIS PAGE LEFT BLANK INTENTIONALLY...

Page 19: ...19 Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual THIS PAGE LEFT BLANK INTENTIONALLY...

Page 20: ...THIS PAGE LEFT BLANK INTENTIONALLY...

Reviews: