3
IntelliChlor Electronic Chlorine Generator COMSYS-10 Installation Guide
Mount Power Center Banks To Wall
(Continued)
4. Remove the cover retaining screw and remove the cover from
upper side left PRIMARY power center and the lower left
side SECONDARY power center.
Connect AC Power Wires and ORP Sensor Wires
1. Mount a JUNCTION BOX on the left
side of the Power Center Banks.
2. Run a CONDUIT (with 208VAC -
260VAC wires) from the AC
BREAKER to the junction box. Note:
This AC power should be on its own
breaker for future servicing.
Note: For 110VAC operations, each
power center will need to be re-
configured. A 110VAC wiring
diagram is provided on the inside of
each the power center covers.
3. Run conduit from the junction box into
each of the power centers located on
the left side (PRIMARY and
SECONDARY). A (knock-out) conduit
opening is provided on the bottom of
each of power centers.
Mount power centers to wall using four
(4) screws
Remove cover screw
and cover
Remove cover screw and cover
Mount power centers to
wall using six (6) screws
CPC103
CPC103
CPC202
CPC202