GW–S Automatic Sprinkler 

SSP, SSU, CUP, WUP,

 

HSW, WHEC  

Heat & Electrically actuated

 (by Metron Actuator ®)

 

 

    

Page 1 of 4 

GW Sprinkler A/S  

Kastanievej 15,                                                                                                                                             Data Sheet No.: 

GW SH060 1001 B

 

DK-5620 Glamsbjerg                                                                                                                       

 

 

e-mail

[email protected]

                                                                                                             Date: 08.02.2017 

web

www.gwsprinkler.com

 

 

 

Nominal Energy                          (Type 1) 

6 millijoules 

Resistance Range (ohms)  

(1)

 

0.9 - 1.6  

Max. No-Fire Current D.C.  

(2)

 

30 sec Pulse 
0.050 sec. Pulse 

 

0.15 amp 

0.3 amp 

Min. Single Firing Current D.C. 

(3)

 

10 ms Pulse 

0.6 amp 
0.9 amp 

Recommended 

Single

 Firing Current

 (4) 

1.0 amp 

Recommended min.

 Series

 Firing Current 

(5)

 

3.0 amp 

Max. Monitoring *) Current (continuous) 

0.01 amp 

 

 
 
 
 
 
 
 
              
             SSP                             SSU                       CUP                   WUP                   HSW                         WHEC 
        (pendent)                    (upright)            (conventional)      (wall U/P)            (window)        (horizontal ext. cov.)  
 
DESCRIPTION 

The GW-S sprinkler series offers high quality, European manufactured, modern compact design, that meet the rigid test 
requirements  set  out  by  the  world  leading  approval  authorities.  The  unique  GW  PTFE  /  double  groove  seal  in 
combination with high end heat responsive frangible glass bulbs guarantee durable operation and reliable performance. 
All  manufacturing  and  testing  processes  are  performed  strictly  in  compliance  with  our  quality  management  system, 
certified to ISO 9001.The use of precisely CNC-machined hot forged frames eliminates the risk of porosity.  
The heat & electrically operated sprinkler is fitted with an electrically operated Metron Actuator that enables instant and 
remote actuation of the sprinkler – typically in combination with a detection system and/or a manually operated switch 
box. 

 
APPLICATION 

GW-S heat & electrically actuated sprinklers are used in fixed fire protection systems. Care must be exercised that RTI, 
orifice  size,  temperature  rating,  deflector  style  and  sprinkler  type  is  in  accordance  with  the  latest  published  sprinkler 
installation standards i.e. EN12845, CEA4001 or NFPA13. 
The GW-S heat & electrically actuated sprinklers are ideal for applications where instant and fully controllable actuation 
of single or multiple heads is called for – e.g. applications involving protection of explosive components/environments.  
 

OPERATION (Metron Actuator) 

The  Metron  Actuator  is  a  highly  reliable,  compact  single  shot  device  which  can  push  with  a  power  to  weight  ratio  in 
excess of 10,000:1. It operates within milliseconds of receiving the appropriate electrical impulse, a rate which is almost 
impossible to achieve with a mechanical source of energy. The short reaction times and high power to weight ratios are 
achieved  by  sophisticated  pyrotechnique.  Within  the  metal  body  of  each  device,  rapid  expansion  of  hot  combustion 
products generates very high pressures which are used to do mechanical work, in this case to drive a piston forward to 
shatter the sprinkler glass bulb. 
Its ability to rapidly convert small electric signals into high mechanical work output, its compact size, high reliability and 
good  environmental  resistance  makes  the  Metron  Actuator  ideal  for  automatic  or  remote  controlled  fire  protection 
applications. 

 
TECHNICAL SPECIFICATION (Metron Actuator) 
 

 

 
 
 
 
 
 
 

 

 

 

 

 

 

                            

        See

 ( )

 notes on next page. 

                                                        *) possibility of the actuator circuit remaining intact after firing must be borne in mind. 

 

 

 

 

 

 

 

Summary of Contents for SSP

Page 1: ... detection system and or a manually operated switch box APPLICATION GW S heat electrically actuated sprinklers are used in fixed fire protection systems Care must be exercised that RTI orifice size temperature rating deflector style and sprinkler type is in accordance with the latest published sprinkler installation standards i e EN12845 CEA4001 or NFPA13 The GW S heat electrically actuated sprink...

Page 2: ...cal sensitivity be mixed in the same circuit Where parallel firing is considered necessary extreme care must be taken to ensure balanced resistances and the possibility of the actuator circuit remaining intact after firing must be borne in mind DEVICE FUNCTION TIME Depends on load and electrical current applied but is typically 10 to 20ms RELIABILITY 0 999 at 95 confidence level ENVIRONMENTAL Work...

Page 3: ... stainless steel OPTIONS For improved corrosion resistance the GW S series can be supplied on request in superior materials such as stainless steel SS316 or 254SMO Nickel Aluminium Bronze and even in Titanium Also available with ENP plating electroless nickel plating SERVICE LIFE The service life of electrically actuated sprinklers is limited by the Metron Actuator to a recommended maximum of 10 y...

Page 4: ...n a flexible conduit for attachment to an electrical junction box Suitable control equipment must be selected based on the Metron Actuator electrical ratings see page 1 When considering the power supply for operating the Metron Actuator be aware that the Metron Actuator after firing may be an open circuit short circuit or connected to earth Therefore it is essential that the power supply be suitab...