3
Alarm Controls:
The alarm level is usually set
above the override level so
the alarm will signal only if the
override level is exceeded.
However, some engineers prefer
to have the alarm level set below
the override level as it is possible
for one pump to fail and the other
pump to operate on the override
level with the sump level never
reaching the alarm level. This is
particularly true in cases of low
inflow capacity.
Electrical Control Panel:
It is recommended that the
Hydromatic control panel be used
with all pumps as proper starter
heaters and connections for heat
sensor wires are furnished.
IMPORTANT:
If Hydromatic
electrical controls are not used
and the motor fails because of
set at turn-on for one pump, and
one set for turn-on for two pumps.
Pumps alternate operation on each
successive cycle.
Two pumps operate together only
if sump level rises to the third or
override control. The override
control also brings on the second
pump in case of failure of the first
pump. Extra floats with
appropriate controls can be
supplied for alarm functions.
Triplex systems use four controls:
one set at turn-off, one set at
turn-on for one pump, one set at
turn-on for two pumps, and
one set at turn-on for three
pumps. Pumps alternate each
successive cycle.
Three pumps operate together
only if sump level rises to the
fourth control (second override).
This control also brings on the
third pump in case of failure
of either or both of the first
two pumps.
improper components or if the
heat sensors are not properly
connected the motor guarantee
is void.
Hydromatic electrical equipment
is installed in a weather-proof
NEMA 3R enclosure. The
electrical equipment includes a
maincircuit breaker for each
pump, a magnetic starter with
overload protection for each
pump, an H-O-A switch and run
light for each pump, an electric
alternator and a transformer to
provide appropriate control
for control circuit and alarms.
Overload Heaters:
If the Hydromatic electrical panel
is not used, starters with 3 leg
overload protection must be
supplied. On 3 phase pumps the
heaters must be sized in
accordance with the nameplate
WIRE SIZE TABLE
FOR REMOTE LOCATION OF CONTROL PANEL LENGTHS ARE BASED ON A VOLTAGE DROP OF TWO PERCENT
Maximum length in feet from NEMA 4 junction box to control panel. For 3 phase only and for power lines only. All control wires can be = 14 –16 or 18 gauge
wire. If power lines are for 460 or 575 volts insulation of control wires must be for this voltage if used in conduit with power lines.
Volts
230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575
Wire
Motor
Size
HP
3
3
3
5
5
5
7
1
⁄
2
7
1
⁄
2
7
1
⁄
2
10
10
10
15
15
15
20
20
20
25
25
25
30
30
30
35
35
35
12
110 450
700
90
370 580
10
180 720 1120 140
550 370
90
360 560
50
220 340
8
270 1100 1650 220
900 1400 175
700 1100 105
420 650
320 500
230
360
180
280
6
400 1600 2500 350 1400 2200 220
900 1400 150
600 930 105
420 650
90 370
570
360
560
320
500
230 360
4
370 1500 2300 230
950 1450 175
700 1100 140 550
850 125 500
800 100 400
620
90 360 560
2
370 1500 230 270 1100 1700 220 900 1400 210 820 1250 200 800 1250 150 600 930
*Special Junction Box required for wire sizes larger than #4.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
System
Number of
Number of
Number of
Type
Control Wires
Power Lines
Ground Wires #8
Number of
Number of
Sensor Wires
Ground Wires
Simplex
3
3
1
3
1
Simplex with Alarm
5
3
1
3
1
Duplex
5
6
1
6
2
Duplex with Alarm
7
6
1
6
2
HEAT SENSOR & SEAL FAILURE
Summary of Contents for Hydromatic S4HRC
Page 11: ...11 S4HRC...