    P545 Series Electronic Lube Oil Control Product/Technical Bulletin 

Troubleshooting 

See Table 2 to troubleshoot the P545 control. 

Table 2: Troubleshooting P545 Control Problems 

LED Status 

Troubleshooting Procedure 

No LEDs are lit. 

Check the power source. 

Red LED is On. 

Common

Signal

12

01

10

12

_p

lu

g.

cd

r

 

WHA-P400-xxx  

Wiring Harness Plug 

Use these steps to resolve the problem: 
1.  Connect pressure gauges at the oil pump discharge and at the crankcase. 
2.  Press RESET on the control. 

a.

  If the green and yellow LEDs light but the compressor remains off

inspect the wiring and check for an overheated motor. If the compressor motor is 

overheated, determine the cause and correct the problem. (An R310AD current 

sensing switch may be installed along with the control to provide a controlled 

shutdown caused by thermal overload.) 
b.

  If both the green and yellow LEDs turn on for the duration of the time 

delay and the system shuts down,

 observe the crankcase and oil pump 

pressure gauges. 

-  If the system does not reach sufficient oil pressure by the end of the time 

delay, check the compressor and system for problems. 

-  If the system does reach sufficient pressure: 

1.  Disconnect the wiring harness at the P400 switch. 
2.  Use a single piece of 22-gauge wire as a jumper between the common 

and signal terminals of the wiring harness. 

3.  Press RESET. 
4.  If the green LED lights and the yellow LED turns off, replace the P400 

switch. Otherwise, replace the P545 control. 

Yellow LED is dim and flickering. 

Use these steps to resolve the problem: 
1.  Check the power source. 
2.  Confirm that the compressor is operating at sufficient pressure and without 

excessive pressure fluctuations. 

3.  Check the wiring harness for loose connections. 
4.  If the oil pressure is sufficient, the cable connections are good, and the yellow 

LED still flickers, replace the P400 switch. 

Control does not lock out the 

compressor when lube oil 

pressure is low. 

Use these steps to resolve the problem: 
1.  Press the test button. 

a.  If the P545 control does not lock out in 8 seconds or less, replace the 

control. 

b.  If the P545 control locks out properly, go to Step 2. 

2.  Disconnect the wiring harness from the P545 control. Press the Reset button. 
3.  If the compressor starts and runs through the time delay (yellow and green LEDs 

lit) and then locks out, check the wiring harness for shorted condition. If the 

wiring harness tests okay, replace the P400 switch.  

Control does not respond to 

R310AD switch. (Control locks 

out the compressor after 

compressor shutdown. Red LED 

is lit.) 

Make sure that the anti-short cycle delay is 

not

 set at 0 seconds. 

 

Summary of Contents for P545 Series

Page 1: ...P545 Electronic Lube Oil Control with P400 Single Point Oil Pressure Differential Switch Features and Benefits Single Pole Double Throw SPDT Relay Contacts for Liquid Line Solenoid and Alarm Applicati...

Page 2: ...ow LED On Compressor contacts close LLS contacts remain closed and alarm remains open green LED On yellow LED On Is the net lube oil pressure sufficient Timer counts down yellow LED Off Green and yell...

Page 3: ...oil pressure is below opening point If the oil pressure is above opening point more than it is below opening point the control does not shut down the compressor If the oil pressure drops continuously...

Page 4: ...the P545 control and the P400 switch 2 When the P445 control is wired to a P400 switch The Test button may operate when first powered up however after a couple minutes of operation the Test Switch fun...

Page 5: ...surfaces of gasket and compressor housing meet 5 Use a torque wrench to tighten the sensor until sealed 40 lb ft recommended torque Wiring See Figure 7 through Figure 12 for typical wiring diagrams o...

Page 6: ...r Diagrams for the P545 Control M1 M2 L2 120 240 P545 NCA NOA CMA L1 L2 L3 Compressor Contactor Wire Jumper Low Pressure Control High Pressure Control Alarm Connection 12011012_8 cdr Figure 8 Typical...

Page 7: ...L3 Compressor Contactor Optional Alarm Connection Low Pressure Control High Pressure Control W1 W2 Remove resistor R39 when using the R310AD switch R39 Power for Alarm Circuit R310AD Switch 12011012_...

Page 8: ...mpressor contactor is energized but the lube oil pressure is below the opening point Timing circuit is active Yellow TIMING LED only Power to the control has been interrupted and restored before the a...

Page 9: ...e supply voltage Reconnect the compressor leads to the contactor or reset the disconnect If an R310AD switch is used reconnect the compressor leads to the contactor See Figure 13 6 Re energize the sup...

Page 10: ...the P400 switch 2 Use a single piece of 22 gauge wire as a jumper between the common and signal terminals of the wiring harness 3 Press RESET 4 If the green LED lights and the yellow LED turns off rep...

Page 11: ...k compressor for internal overloads 2 Check the compressor wiring 3 Check compressor s contactor 4 Check compressor for general failure Ordering Information Use the following tables to order the P545...

Page 12: ...3 ft 1 m length wiring harness WHA P400 125C 4 ft 1 1 4 m length wiring harness WHA P400 250C 8 ft 2 1 2 m length wiring harness WHA P400 430C 14 ft 4 1 3 m length wiring harness R310AD 1C Low Voltage...

Page 13: ...240 VAC Backplate Material Case and Cover Material Cold rolled steel High impact thermoplastic Ambient Operating Conditions 40 to 131 F 40 to 55 C Ambient Storage Conditions 40 to 185 F 40 to 85 C App...

Reviews: