Setup and adjustments

Important:

• Do not adjust the pointer beyond the highest

or lowest indicator marks on the control’s

temperature scale. Adjusting the pointer beyond

the indicator marks may damage screw threads,

may cause inaccurate control operation, and

voids the warranty. Also, most controls with

spot sensitive sensing elements used for coil

protection are set and sealed at 35°F (1.6°C).

Attempting to set them lower can damage the

control.

• After adjusting the control settings and before

leaving installation, verify equipment and control

operation, and verify control setpoint with a

reliable thermometer.

Adjust the setpoint by turning the adjustment screw until

the pointer is opposite the cutout point that you want.

Access the adjustment screw at the bottom of the control

or at the top when you remove the cover.

Checkout procedure

Before you leave the installation, observe at least

three complete operating cycles to make sure that all

components function correctly. When used as a low

temperature cutout control, simulate operation by

actuating contacts to confirm that electrical connections

are correct.

Operation

The A11D and A11E models have SPDT contact action;

models A11A and A11B have SPST contacts. When 16 in.

(406 mm) or more of an A11 control’s sensing bulb senses

a temperature equal to or lower than the setpoint, the

contacts open on SPST controls, or the circuit between the

Red and Yellow terminals open on SPDT controls.
The A11A and A11D models lock out when the

temperature decreases below the control’s temperature

setpoint. Manual reset is a requirement of these models.

Press and release the reset lever after the temperature

increases 12F° (6.7C°) or more above the setpoint in order

to reset. The A11B and A11E automatically reset on an

increase in temperature.

Note: 

A11 Series low temperature cutout controls

have 6.1 m of 3.2 mm O.D. tubing and 1.2 m capillary

(20 ft of 1/8 in. O.D. tubing and 4 ft capillary.)

Table 6: A11 Series Low Temperature Cutout Controls

Code
number

Switch
action

Range

Differential

Maximum
bulb
temperature

Range
adjuster

A11A-1C

Manual reset

A11B-1C

SPST
open low

6.7°F (12°C) fixed

A11D-5C

Manual reset

A11E-5C

SPDT

35°F to 45°F
(2°C to 7°C)

6.7°F (12°C) fixed

250°F (121°C) Screwdriver

slot

Repair Information

If the A11 Series Low Temperature Cutout Control fails

to operate within its specifications, replace the unit. For

a replacement A11 Series Control, contact the nearest

Johnson Controls

®

 representative.

A11 electrical rating

Table 7: A11 Series electrical rating

Description

cULus

Volts AC 50/60 Hz

120

208

240

Full load amperes

16

9.2

8

Lock rotor amperes

96

55.2

48

Resistive amperes

16

9.2

8

Pilot duty

125 VA, 24 VAC to 277 VAC

A11 Series Low Temperature Cutout Control Installation Guide

6

Summary of Contents for A11 Series

Page 1: ...tream side of the coil Expose the element to all areas where low temperatures may occur 2 Horizontally serpentine the 20 ft 6 1 m long sensing element across the face of the coil to sense temperatures...

Page 2: ...u mount the control below the sensing element prevent possible nuisance alarms by mounting the control in a conditioned space When using the A11 Series control coil the excess capillary inside the con...

Page 3: ...f the entire installation Mount the control upstream from mixed air or chilled water coils Mount the control downstream from preheat coils Mount the control upright on flat vertical or horizontal surf...

Page 4: ...ly sleeve around the capillary at the point where it passes through the entry hole in the duct work Slit the tubing lengthwise to permit easy installation You do not normally need caulking or sealant...

Page 5: ...that you can position the capillary whip close to the support See Figure 6 11 Place a 4 in 10 1 cm box cover with the center knockout removed over the upper end of the support assembly and use a lock...

Page 6: ...lb senses a temperature equal to or lower than the setpoint the contacts open on SPST controls or the circuit between the Red and Yellow terminals open on SPDT controls The A11A and A11D models lock o...

Page 7: ...1 2 in 12 7 mm trade size or PG16 conduit Ambient conditions 0 F 18 C to 140 F 60 C Compliance North America cULus listed UL60730 CSA E60730 File SA516 Product warranty This product is covered by a l...

Page 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Reviews: