background image

Mounting in an inaccessible location

1. Determine the mounting location for the low limit

control.

- Avoid any moving parts within the duct, such

as dampers.

- When the duct is covered with insulation,

mount the control to a standard electrical

4- square box and cover.

2. Using Figure 5 as a guide, measure the duct and

calculate the required length and height of the

element support.

3. Use 1/2 in. (1.3 cm) of EMT to build the support

assembly outside of the duct.

Note: 

You can substitute 3/8 in. (1 cm) of

hard copper tubing for 1/2 in. (13 mm) of

EMT when you build the support. These

instructions assume the use of EMT.

4. Starting at the bottom of the coil, distribute the

sensing element around the support and use a tie-

wrap to secure it in place. Keep the loops horizontal

or inclined slightly downward at an angle not

greater than 5° and uniform in size (see Figure 5).

5. Consider the use of Minerallac conduit hangers

or equivalent to provide anchoring points on the

support where needed.

6. Place a 1/2 in. (1.3 cm) EMT connector on each end

of the support. These connectors protrude through

the knockout hole on the 4 in. (10.1 cm) box covers,

which are used as mounting plates at each end of

the support.

7. At the upper end of the duct, use a large hole saw

of minimum size 2-1/4 in. (57 mm) to drill the entry

hole for the sensing element or support assembly.

8. At the lower end of the duct, drill another hole. Use

the same hole saw that you used to cut the entry

hole.

9. A larger hole provides easier access for mounting.

Position this hole so that the lower portion of the

sensing element is within 6 in. (152 mm) of the

bottom of the coil.

10. Cut a notch in another 4 in. (10.1 cm) box cover.

Use the notch to secure the upper end of the

support assembly. Locate the notch so that you can

position the capillary (whip) close to the support.

See Figure 6.

11. Place a 4 in. (10.1 cm) box cover, with the center

knockout removed, over the upper end of the

support assembly, and use a lock nut to fasten the

support to the box cover.

12. Feed the sensing element or support assembly

through the entry hole at the upper end, and

position the lower end of the support to protrude

through the exit hole at the bottom on the far side.

13. Place a 4 in. (10.1 cm) box cover with the center

knockout removed over the end of the support and,

using a lock nut, fasten the support in place at the

lower end.

Figure 6: 4-square cover upper mount with center 1/2

in. knockout.

Table 5: 4-square cover upper mount callouts

Callout Description

A

Use a hacksaw to cut a slot for the

sensor to pass through.

B

Use a drill to cut a 1/4 in. hole. Cover the

element with poly for protection.

C

To secure 1/2 in. EMT to the box cover.

14. Carefully place the capillary tube in the slot and

apply a short piece of 1/4 in. (6.4 mm) poly tubing,

slit lengthwise, around the capillary where it passes

through the notch.

15. Screw down the corners of the box cover to hold

the upper end of the support assembly in place.

16. Use the mounting bracket and self-tapping screws

to fasten the control to the side of the duct,

ensuring a downhill element all the way to the

bottom of the control.

Wiring

For most AHU installations, it is more cost-effective to wire

the low limit and other safeties with low voltage Class 2

wiring and add a shutdown relay at the motor starter.
This practice provides the control to share raceways with

other low voltage cables for the system.

 CAUTION

Risk of Electric Shock

Disconnect power supply before making electrical

connections to avoid electric shock.

Important: 

Make all wiring connections in

accordance with local, national, and regional

regulations. Do not exceed the electrical ratings.

A11 Series Low Temperature Cutout Control Installation Guide

5

Summary of Contents for A11 Series

Page 1: ...tream side of the coil Expose the element to all areas where low temperatures may occur 2 Horizontally serpentine the 20 ft 6 1 m long sensing element across the face of the coil to sense temperatures...

Page 2: ...u mount the control below the sensing element prevent possible nuisance alarms by mounting the control in a conditioned space When using the A11 Series control coil the excess capillary inside the con...

Page 3: ...f the entire installation Mount the control upstream from mixed air or chilled water coils Mount the control downstream from preheat coils Mount the control upright on flat vertical or horizontal surf...

Page 4: ...ly sleeve around the capillary at the point where it passes through the entry hole in the duct work Slit the tubing lengthwise to permit easy installation You do not normally need caulking or sealant...

Page 5: ...that you can position the capillary whip close to the support See Figure 6 11 Place a 4 in 10 1 cm box cover with the center knockout removed over the upper end of the support assembly and use a lock...

Page 6: ...lb senses a temperature equal to or lower than the setpoint the contacts open on SPST controls or the circuit between the Red and Yellow terminals open on SPDT controls The A11A and A11D models lock o...

Page 7: ...1 2 in 12 7 mm trade size or PG16 conduit Ambient conditions 0 F 18 C to 140 F 60 C Compliance North America cULus listed UL60730 CSA E60730 File SA516 Product warranty This product is covered by a l...

Page 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Reviews: