Unit
Set the unit of measurement, for example kN or N. This will be shown everywhere the measured
force is displayed or printed.
Stable
The stable settings determine when the indicator accepts the current value as stable.
Stable range
Set the range the indicator has to be in for the set time to give a stable signal.
Stable time
Set the time the weigher has to be within the range to give the stable signal.
With these values, the indicator has to be within the range of 0,002kN over the time of 1,00
second to indicate stable. When stable, the stable indication on the display will light up.
Zero tracking
Zero tracking is able to tune the zero point back to zero when the scale becomes dirty.
Tracking range
Set the maximum offset to tune back to zero.
Tracking step
Set the step size that will be tuned every time the force is within the tracking range.
Tracking time
Set the time that the force has to be within the tracking range to tune 1 step back to zero.
With these values, the indicator will step back 0,010kN towards zero every 1,00 second as soon
as the measured force gets below 0,100kN.