PT495 Series Detector
(Ultra1000)
Rev 5.11
26
Configuration Menu
The configuration menu above has 3 options, Set address, Low Alarm Level and
High Alarm level. Last option is to Exit. These options are scrolled on the display
screen one at a time. To select the displayed option simply place and hold the
magnet on the right side of the enclosure for 2 to 3 seconds. After selecting the
option edit the data value by holding the magnet to its place. Remove magnet to
end the data edit mode and return back to configuration options list.
Edit
Config….
Set
Address.
Set
Low Alarm
Set
Hi Alarm
Exit ?
Set a unique address of the detector.
Address set between 1 and 120
Address
1
Low Alarm
10
Hi Alarm
15
Set Low alarm Level between 0 and full
scale range. Set to 0 to disable Low
alarm relay
Select to exit the configuration menu.
Else menu will scroll back on top of menu
Set High alarm Level. Set level
between 0 and full scale range. Set
to 0 to disable Hi alarm relay