4.3 The determination of the installation method and position
4.3.1 Mounting method
Please mount the inverter correctly.
1. The equipment employs natural convection cooling and regulated
ventilation, it can be installed indoor or outdoor.
2. Please install the device as shown in the figure. Vertical installation on floor
level is recommended. Mount vertically or tilted backwards by max. 15°. Never
install the inverter tilted forwards, sideways, horizontally or upside down.
3. Install the inverter at eye level for convenience when checking the LCD
display and possible maintenance activities.
4. When mounting the inverter, please consider that disassembly for service
work may be required.
4.3.2 Installation position
Do not expose the inverter to direct solar irradiation as this could cause power
derating due to overheating.
The ambient temperature should be between -25°C - +60°C (-13°F - 140°F) to
ensure optimum operation. Choose locations with sufficient air exchange.
Ensure additional ventilation, if necessary.