DIN NANO FSC
Annexes
USER AND MAINTENANCE MANUAL
Rev. 03-18
Page 26
CONNECTION DIAGRAM
Power supply section
1-2:
power supply 230 Vac 50/60Hz
Section of digital outputs (voltage-free contacts)
3-4:
(RL5)
General alarm
( Relay 8A AC1 250V contact N.O.)
5-6:
(RL1)
N.1 output
( Relay 16A AC1 250V contact N.O.)
7-8:
NOT USED
9-10:
NOT USED
11-12:
NOT USED
Analogue Output Section
13:
(COM_OUT_AO1) Common analogue output
(Rif 0) - (gnd)
14:
(OUT_AO1)
Condenser fans
(Analogue output 0-10V)
Master interface section - Slave - Console
15:
(RS485-B)
RS485-B Lan for Telenet / ModBus
16:
(RS485-A)
RS485-A Lan forTelenet / ModBus
Section of digital inputs
17:
(DI1)
Digital input nr.1
18:
(COM DI1)
Common (GND) digital input n.1
Section of analogue inputs
19:
(COM DI2)
Common (GND) digital input nr.2
20:
(DI2)
Digital input nr.2
If mOd = 0 or mOd = 3:
21:
(COM DI3)
Common (GND) digital input nr.3
22:
(DI3)
Digital input nr.3
If mOd = 1 or mOd = 2:
21:
(COM DI3)
Common (GND) analog input AI2
22:
(DI3)
Analog input NTC (10K
Ώ 1% a 25°C) external ambient probe
If Pt=0:
23:
(COM AI1)
12Vdc) Analogue input AI1
24:
(AI1)
Analogue input (4-20mA ) for Adjustment pressure probe
If Pt=1:
23:
(COM AI1)
Common (GND) analog input AI1
24:
(AI1)
Analog input NTC (10K
Ώ 1% a 25°C) for Adjustment temperature probe
NOTE:
Inside the circuit board, there are bridges
already configured for the correct reading of
the digital and analogue inputs of the board.
Their setting must not be changed under
any circumstances.
Manufacturer settings of the bridges for the
200NDINFSC:
J31=1-2
J32=1-2
J21=1-2
J22=1-2
If 4-20mA:
J11=2-3
J12=2-3
Se NTC:
J11=1-2
J12=1-2
Manufacturer settings:
J31=1-2
J32=1-2
J33=open
J21=1-2
J22=1-2
J23=open
J11=2-3
J12=2-3
J13=open
A.2