Pego 200NDINFSC User And Maintenance Manual Download Page 18

     

 DIN NANO FSC 

 

 

            

Chapter 5 

– Data Programming

 

 

                                                                                                                                                                                                                                                                                                                                                                                                                                         

 

USER AND MAINTENANCE MANUAL 

 

Rev. 03-18

 

Page  18

 

 

OPERATING MODE 

 
The condenser fans are controlled via a 0-10V analogue output and sideband-type adjustment. 
The LED icon (11) turns on to identify the fan condenser control. 
The regulation probe (terminal 23 /24) can be of two types: 

Flow pressure probe 4-20mA (parameter Pt = 0).  

Condensing temperature probe NTC 10K

Ω (parameter Pt = 1). 

The  setting  of  parameter  Pt  according  to  the  type  of  probe  connected  must  be  combined  with  the  correct 
setting  of  the  jumpers  on  the  NDINFSC  board  (see  connection  diagram).  Changing  the  Pt  involves  loading 
the  relevant  default  paramet

ers  on  the  variables  marked  with  an  asterisk  in  the  “default  Pt”  column  and 

changing the unit of measure of some parameters (Bar if the probe connected is a pressure probe, °C if the 
probe connected is a temperature probe). There are various fan control modes available. 
 
 

CONTROL IN THE EVENT OF ALARMS   

 
With the presence of ‘fans alarm’, the analog output is immediately brought to 0V and then open the digital 
output 1 (inverter off). In addition, the display shows alarm (Ev). 
 
 

NORMAL MODE (mOd = 0) 

 

The  adjustment  follows  the  operation  of  graph  nr.1  with  the  increase  of  the  output  pressure/condensing 
temperature  and  the  decrease  of  graph  nr.2.  For  simplicity,  we  define  the  value  of  the  probe  pressure  / 
temperature as adjustment probe. 
 

 
Adjustment probe value INCREASE 

(Graph nr.1):  

 
 The  analogue  output  of  the  adjuster  will  be 
0V for output pressure probe less or equal to 
point  (B)  representing  the  "SET  point  +  iOv 
offset" value. 
If  the  adjustment  probe  value  is  higher  than 
point  (B),  you  will  have  the  analogue  output 
at  (iHv)  for  the  maximum  BOv  time.  BOv  is 
the  Fans  Boost  times  for  which  the  adjuster 
output is  increased  by  100% in order to help 
the start-up of the fans. 
Between  points  (B)  and  (C),  the  analogue 
output  will  have  a  value  proportional  to  the 
value  of  the  adjustment  probe  starting  from 
the minimum value of the parameter (iLv) up 
to the maximum value of the parameter (iHv).  
With adjustment  probe  value  equal  or  higher 
than point (C), you will have a (iHv) analogue 
output. 
Digital output nr.1 represents "the condenser 
fans  inverter  activation"  and  is  ON  for 
adjustment  probe  value  higher  than  or  equal 
to the set point and OFF for lower values. 
 
 
 

 
 
 

5.12 

Graph. nr.1 

5.12.1 

Summary of Contents for 200NDINFSC

Page 1: ...NANO FSC USER AND MAINTENANCE MANUAL Page 1 User and maintenance manual ENGLISH ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS READ AND KEEP REV 03 18 ENG 200NDINFSC Electronic regulator on DIN ba...

Page 2: ...ng the set point Page 12 5 6 Level 1 programming Page 12 5 7 List of Level 1 variables Page 14 5 8 Level 2 programming Page 14 5 9 List of Level 2 variables Page 17 5 10 Level 3 programming Page 17 5...

Page 3: ...eed MAIN FEATURES 0 10 V analog output for speed control of the condenser fans Regulation with pressure or temperature probe Acquisition of outside temperature to optimize the control 4 operating mode...

Page 4: ...Page 4 OVERALL DIMENSIONS Dimensions in mm IDENTIFICATION DATA The device described in this manual has a plate on one side bearing the identification data Name of Manufacturer Code and model of the d...

Page 5: ...and digital inputs in these 4 Minimize the length of the connecting cables to prevent these from coiling up and adversely affecting the electronics through induction 5 All the conductors of the cable...

Page 6: ...the module on the DIN guide and close the bottom clamp to hold it in place Make all the electrical connections with reference to the diagrams of the relative model see the relative tables in the ANNE...

Page 7: ...tible type of temperature sensor NTC 10Kohm 1 25 C Output features voltage free contact Description Relay installed Features of output board Fans enable Relay 16A AC1 16 6 A 250V Not used Relay 16A AC...

Page 8: ...efused when the equipment is modified or transformed Under no circumstances Pego S r l will be liable for any loss of data and information costs of goods or substitute services damage to property peop...

Page 9: ...for more than 1 second the Stand by state will alternate with the normal operating status and vice versa In the stand by state the system stops and the display will change the writing OFF with the cur...

Page 10: ...analogue output 6 6V 9 PRG ICON Flashing LED Programming or SET POINT change 10 11 CONDENSER FAN CONTROL ICON LED ON Condenser Fan Control ENABLED 12 UNIT OF MEASURE IN DEGREES CELSIUS ICON LED ON Un...

Page 11: ...mming menu To exit the menu press the up and down arrow keys together LEVEL 3 PROGRAMMING Pressing both keys together for more than 3 seconds enables access to the Level 3 programming menu To exit the...

Page 12: ...OWN key for over 3 seconds When the first programming variable appears 1 Select the variable you want to change with the key or with the key After selecting the required variable it is possible to 2 V...

Page 13: ...obe below which once the Ald delay time is activated the LOW pressure alarm is triggered showing EL alternating with the pressure temperature on the display and the flashing of the alarm icon When the...

Page 14: ...d 1 Fans enabling fans 0 with DI 0 2 Energy saving active night with DI 0 3 Fans alarm fans 0 with DI 0 4 High pressure fans 100 with DI 0 1 In2 Settings of nr 2 Digital input 4 High pressure fans 100...

Page 15: ...t 0 and mOd 1 45 0 HSE 0 2 C step 0 2 C with Pt 1 45 0 C HSE Maximum value that can be attributed to set point with Pt 0 LSE 0 2 90 0 Bar step 0 2 Bar with Pt 0 25 0 Bar with Pt 1 or Pt 0 and mOd 1 LS...

Page 16: ...ud 6 14400 baud 7 19200 baud 8 38400 baud 5 Prt Modbus parity checking 0 no parity bit 1 even parity bit 2 odd parity bit 0 P1 Password type of protection Active when PA is not 0 0 shows only the set...

Page 17: ...3 VARIABLES Installer Level LABEL MEANING VALUES DEFAULT default Pt Pt Adjustment probe type PLEASE NOTE the Pt Exchange involves loading default settings dedicated on the variables marked with an as...

Page 18: ...output 1 inverter off In addition the display shows alarm Ev NORMAL MODE mOd 0 The adjustment follows the operation of graph nr 1 with the increase of the output pressure condensing temperature and t...

Page 19: ...adjustment probe value higher than or equal to the set point and OFF for lower values ENERGY SAVING MODE mOd 1 In this mode the control modifies the Set point according to the external temperature Whe...

Page 20: ...speed of the fans increases as the external temperature by combining a variation of the external temperature equal to dAt with a variation of the minimum control voltage equal to iMV iLV To take adva...

Page 21: ...perating curve according to the external temperature FIXED SPEED MODE mOd 3 In this mode the 0 10 V fan control output takes on a fixed value equal to parameter iMv The enabling analogue output and di...

Page 22: ...en the keypad is not used for 30 seconds The digits 000 appear on the display Use the up down arrow keys to edit the number and press the SET key to confirm The 000 password window disappears if the k...

Page 23: ...rument In detail Ad address shows regulation temperature probe value TWMT regulation pressure probe value TWMP converted regulation temperature probe value TWMT Ad 1 address shows external ambient tem...

Page 24: ...OM ALARM An error was found in the EEPROM memory The outputs are all disabled apart from the alarm outputs Switch the appliance off and back on If the problem persists replace the Control Circuit Boar...

Page 25: ...mpatibility EMC 2014 30 EU LA CONFORMITA PRESCRITTA DALLA DIRETTIVA E GARANTITA DALL ADEMPIMENTO A TUTTI GLI EFFETTI DELLE SEGUENTI NORME THE CONFORMITY REQUIRED BY THE DIRECTIVE IS GUARANTEED BY THE...

Page 26: ...GND digital input nr 2 20 DI2 Digital input nr 2 If mOd 0 or mOd 3 21 COM DI3 Common GND digital input nr 3 22 DI3 Digital input nr 3 If mOd 1 or mOd 2 21 COM DI3 Common GND analog input AI2 22 DI3 An...

Page 27: ...Annexes DIN NANO FSC Page 27 USER AND MAINTENANCE MANUAL Rev 03 18 REMARKS...

Page 28: ...Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 Fax 39 0425 762905 e mail info pego it www pego it AFTER SALES ASSISTANCE CENTRE Tel 39 0425 762906 e mail tecnico pego it Distributor...

Reviews: