Peco Performance pro T4000 series Installation Manual Download Page 6

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 01

6

PECO Wave PRO and PECO are registered trademarks of PECO, Inc. The PECO logo is a trademark of PECO, Inc.

To access Service Menus, simultaneously press lower left and lower right keys. Changed values are automatically retained. Service Menu availability is dependent upon system type and 

upon system configuration. Note: The Remote Indoor Zone Sensor must be enabled in the Service Menus (see Service Menu 170). 

menU

 

FeatUre

oPtIons

stD.moDel 

DeFaUlt

DescrIPtIon / comments

100*

Schedule Format

0-3

1

Select the schedule format on the Performance PRO T4000 Series.

0 =   nonprogrammable 

1 =   programmable

2 =   5-1-1 schedule 

3 =   5-2 schedule 

101

Daylight-Saving 

Time

0,1

0

Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at 

2:00 AM and ends on the first Sunday of November at 2:00 AM. 

0 =   Disabled 

1 =    Enabled (2007 US Format)

110

System Type

1-11

1

Select the appropriate system configuration (determines available Service Menus). 

1 =   1 Heat/1 Cool conventional

2 =   1 Heat/1 Cool heat pump

3 =   Heat only without fan (2-wire systems)

4 =   Heat only with fan

5 =   Cool only

6 =   2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat

7 =   2 Heat/2 Cool multistage conventional

8 =    2 Heat/ 1 Cool multistage conventional

9 =    1 Heat/ 2 Cool multistage conventional

10 =   2 Heat/ 2 Cool heat pump (no aux. heat)        

11=   3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat

120

Fan Control 

(heating)

0,1

0

0  =   Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan)

1  =   Electric Furnace (thermostat controls heating fan)

130

Changeover valve 

(B/O terminal)

0,1

0

0 =   B/O terminal controls valve in cooling

1 =   B/O terminal controls valve in heating

140

Auxiliary Heat

0,1

0

0 =   Electric backup heat

1 =   Fossil fuel backup heat

150

Backlight

0,1

0

0 =   Backlight temporarily on

1 =   Backlight always on (low intensity, 24V only)

170

Remote Sensor

0-1

0

Select sensor if used (connected to the S1 Terminal). Contact PECO for more information on the Indoor 

Remote Zone Sensor.

0 =   No Sensor 

1 =   Indoor Sensor 

230

Furnace Filter 

Change Reminder

0; 30; 60; 90; 

120; 365

0

Set a filter reminder timer; appears on digital display when timer expires (if programmed).

0 =   Off

10 days; 30 days; 60 days; 90 days; 120 days; 365 days

240

Number of Program 

Periods

2; 4 events

4

2 =   2 events per day

4 =   4 events per day

250

Clock format

12 or 24 Hours

12

12 =   12-hour clock mode

24 =   24-hour clock mode

260

Temperature Format 

(°F or °C)

0,1

1

0 =   Celsius

1 =   Fahrenheit 

270

Fan Off Delay Heat

0-99 Seconds

0

Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned 

off.

280

Fan Off Delay Cool

0-99 Seconds

0

Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned 

off.

290

Range Low

50-90 °F or 

10-32°C

50°F (10°C)

Choose the lowest selectable temperature setpoint value.

300

Range High

50-90 °F or 

10-32°C

90°F (32°C)

Choose the highest selectable temperature setpoint value.

310

Setback Low

Off; 50-82°F or 

11-27°C

55°F (13°C)

Select the heat setpoint for setback mode.

0 =   Off

50-82°F (11-27°C) 

320

Setback High

Off; 58-90°F or 

11-32°C

90°F (32°C)

Select the cool setpoint for setback mode. 

0 =   Off

58-90°F (11-32°C)

330

Zone Temp Offset

 +/-9°F or +/-

4.5°C

0°F (18 °C)

Adjusts the displayed value; may differ from actual zone temperature. 

taBle 2. aDvanceD conFIGUratIon: servIce menUs 

Summary of Contents for Performance pro T4000 series

Page 1: ...d heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Perman...

Page 2: ...n SC Sensor Common S1 Indoor Remote Sensor S1 Indoor Remote Sensor S2 Occupancy Setback Input S2 Occupancy Setback Input System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TE...

Page 3: ...llplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper conn...

Page 4: ...Ith sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more t...

Page 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in t...

Page 6: ...trols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fue...

Page 7: ...duled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for...

Page 8: ...isable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Page 9: ...esent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is o...

Page 10: ...mount peco indoor remote zone sensor sP155 017 WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply w...

Page 11: ...or maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG...

Page 12: ...r message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1...

Page 13: ...eratura de funcionamiento 0 a 120 F 17 a 48 C Temperatura de env o 20 a 130 F 28 a 54 C Humedad durante el funcionamiento 5 a 95 RH no condensante Dimensiones f sicas Termostato T4000 T4500 pantalla d...

Page 14: ...Sensor com n S1 Sensor remoto interior S1 Sensor remoto interior S2 Sensor de ocupaci n S2 Sensor de ocupaci n Tipo de sistema 1 1C 1F Convencional Tipo de sistema 2 1C 1F Bomba de calor TERMINAL Func...

Page 15: ...de que el puente permanezca en su lugar transformador doble del sistema El T4000 T4500 se env a con un puente que conecta las terminales RH y RC Si el equipo de calefacci n y de refrigeraci n no util...

Page 16: ...el funcionamiento del termostato Siga al menos un procedimiento en las pruebas de sistema a continuaci n Consulte los Men s de Servicio vea la Tabla 2 para m s pruebas Para todas las pruebas oprima n...

Page 17: ...lla vea la Fig 14 2 Oprima Next siguiente hasta que el Men de Servicio 341 Acceso PIN para activar o desactivar se muestre en la pantalla El valor predeterminado de 00 aparece debajo del Men de Servic...

Page 18: ...0 1 0 0 La terminal B O controla la v lvula en la refrigeraci n 1 La terminal B O controla la v lvula en la calefacci n 140 Calor auxiliar 0 1 0 0 Calor de reserva el ctrico 1 Calor de reserva de comb...

Page 19: ...ordatorio de tiempo hasta el pr ximo evento programado 1 1 hora 2 2 horas 3 3 horas 4 4 horas 400 Ciclos por hora CPH Etapa de refrigeraci n 1 0 6 CPH 3 CPH Define un n mero de ciclos por hora para re...

Page 20: ...r 1 Activar Nota Oprima la tecla Done finalizar para completar el proceso 600 Salida principal de la prueba de sistema Fr o 0 2 0 Seleccione una opci n para activar la salida del ventilador por 10 min...

Page 21: ...Indicador de Demanda aparece de color rojo Est funcionando la calefacci n No se necesita realizar ninguna acci n Si la luz del Indicador de Demanda aparece de color verde Est funcionando la refrigera...

Page 22: ...ADVERTENCIA LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INTENTAR INSTALAR OPERAR O DARLE MANTENIMIENTO A ESTE SENSOR El incumplimiento de la informaci n de seguridad y de las instrucciones puede...

Page 23: ...e 18 De 386 a 610 pies de 117 6 m a 185 9 m calibre 16 De 611 a 970 pies de 186 2 m a 295 6 m calibre 14 caBleaDo 1 Funcionamiento de los cables Tienda los cables entre la placa de pared del termostat...

Page 24: ...na interna no est conectado de manera apropiada verifique lo siguiente Aseg rese de que los cables del sensor est n conectados de manera apropiada a las terminales S1 y SC en la placa de pared del ter...

Page 25: ...WG ou un fil rigide Temp rature de fonctionnement 17 48 0 120 F Temp rature de transport 28 54 C 20 130 F Humidit de fonctionnement 5 95 d humidit relative sans condensation Dimensions Thermostat T400...

Page 26: ...rieur S2 Capteur de r glage d occupation S2 Capteur de r glage d occupation Type d installation 1 Conventionnel 1H 1C Type d installation 2 Pompe chaleur 1H 1C TERM Fonction TERM Fonction C Commun C C...

Page 27: ...al relie RC et RH Connectez le c t de l alimentation au RC RH et veillez ce que le cavalier reste en place syst me double transformateur Le T4000 T4500 est livr avec un cavalier qui relie les bornes R...

Page 28: ...e proc dure des tests syst me ci dessous Consultez les menus de configuraton voir tableau 2 pour plus de tests Pour tous les tests cliquez sur next Suivant pour passer au test syst me suivant qui est...

Page 29: ...min s affichent voir figure 14 2 Appuyez sur Next Suivant jusqu ce que le menu de configuration 341 Activer D sactiver l acc s par code NIP s affiche l cran La valeur par d faut 00 s affiche en dessou...

Page 30: ...contr le le ventilateur d air chaud 130 Valve de basculement Terminal B O 0 1 0 0 La borne B O commande la valve de climatisation 1 La borne B O commande la valve de chauffage 140 Chauffage auxiliair...

Page 31: ...4 heures 400 Cycles par heure CPH 1 re phase de climatisation 0 6 CPH 3 CPH D finit le nombre de cycles par heure pour la climatisation Phase 1 S lectionnez 0 pour activer le contr le ON OFF MARCHE AR...

Page 32: ...e la sortie principale Climatisation 0 2 0 S lectionnez une option pour activer la sortie du ventilateur pendant 10 minutes s lectionnez 0 Done Termin ou un autre menu de configuration pour d sactiver...

Page 33: ...nde est rouge Le chauffage ne s enclenche pas Aucune action n est requise Si le voyant t moin de demande est vert La climatisation s enclenche Aucune action n est requise Si le voyant t moin de demand...

Page 34: ...017 AVERTISSEMENT LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT DE TENTER D INSTALLER DE FAIRE FONCTIONNER OU DE R PARER CE CAPTEUR N gliger de respecter les informations sur la s curit et les instructio...

Page 35: ...117 m tres Calibre 18 117 185 m tres Calibre 16 186 295 m tres Calibre 14 c BlaGe 1 Faites courir les fils Faites courir les fils entre la plaque murale du thermostat et le panneau de montage du capte...

Page 36: ...s suivants Assurez vous que le capteur est install correctement et raccord aux bornes S1 et SC sur la plaque murale du thermostat voir le tableau 1 D signations des bornes et Types de syst mes Si vous...

Reviews: