PCS PCS 4000 User Manual Download Page 7

USER GUIDE

7

PCS 4000 

SINGLE WELL CONTROLLER

How pressure operation works

When set to a pressure operating mode, the controller 
opens the A-valve based on the difference between 2 
pressure values. The pressure values used are:

Mode 1: Time only input (no pressure)

 

„

Mode 2: Tubing pressure minus sales line pressure

 

„

Mode 3: Casing pressure minus tubing pressure

 

„

Mode 4: Casing pressure minus sales line pressure

 

„

Note:

 When set to Mode 1 or time mode, the controller 

opens and closes the A-valve and B-valve based on time 
input. It does not respond to pressure input or flow rate 
input.

Here are the steps in the pressure operation cycle.

1  The controller closes the A-valve and counts down the 

FALL TIME (SET 05). This gives the plunger time to fall 
to the bottom of the well. The status display shows 
CLOSE 0:00:00.

Note:

 CLOSE TIME is normally set to 00:00:00 because 

the controller opens the A-valve in response to 
changes in pressure.

2  While the A-valve is closed, the casing pressure and 

tubing pressure rise.

3  The controller monitors:

Tubing pressure minus line pressure differential in 

 

ƒ

Mode 2
Casing pressure minus tubing pressure differential 

 

ƒ

in Mode 3
Casing pressure minus line pressure differential in 

 

ƒ

Mode 4

The controller opens the A-valve when:

The difference between the 2 pressures is equal 

 

ƒ

to or greater than the DIFFERENTIAL OPEN 
PRESSURE (SET 12) value (see “DIFFERENTIAL 
OPEN PRESSURE” on page 9), 

and

The FALL TIME countdown reaches zero.

 

ƒ

If the DIFFERENTIAL OPEN PRESSURE value is 
reached during the FALL TIME countdown, the status 
display shows the FALL TIME remaining.

Note:

 You can use any “open” function together with or 

in place of DIFFERENTIAL OPEN PRESSURE. After the 
FALL TIME countdown has reached zero, the controller 
opens the A-valve as soon as it receives input from any 
“open” function. For more information, see “Features 
for Opening the A-Valve” on page 11
.

4  The controller opens the A-valve and counts down the 

OPEN TIME (SET ON).

If the plunger arrives during the OPEN TIME 

 

ƒ

countdown, the controller goes to step 6.
If the plunger does not arrive during the OPEN TIME 

 

ƒ

countdown, the controller goes to step 5.

5  The controller opens the optional B-valve and counts 

down the B OPEN TIME (SET B ON).

If the plunger arrives during the B OPEN TIME 

 

ƒ

countdown, the controller goes to step 6.
If the plunger does not arrive during OPEN TIME or 

 

ƒ

B OPEN TIME, the controller closes the A-valve and 
B-valve and counts down the MANDATORY SHUT-
IN TIME (SET 03). When this countdown reaches 
zero, the controller goes to step 4.

Note:

 If the well has liquid trailing behind the plunger, 

you may want to set B DELAY TIME. See “B DELAY 
TIME” on page 13 for more information.

6  The controller counts down the DELAY TIME (SALES) 

(SET 02) while monitoring the casing pressure, flow 
rate, or both.

Note:

 DELAY TIME (SALES) is the maximum time the 

well is allowed to stay open after the plunger arrives. 
The controller responds to the first input to close the 
well. The close input may be:

Casing pressure – see 

 

ƒ

step 7.

Low flow rate – see 

 

ƒ

page 12.

Critical flow K factor – see 

 

ƒ

page 12.

DELAY TIME (SALES) countdown reaches zero – 

 

ƒ

see page 13.
Another close input unrelated to casing pressure, 

 

ƒ

low flow rate, critical flow K factor, or time. For 
example: low or high sales line pressure, a manual 
input to close the well, and so on.

7  Casing pressure normally drops while the plunger 

rises. When the casing pressure starts to build, the 
controller monitors the increase in pressure. When 
the increase equals the DIFFERENTIAL CLOSE 
PRESSURE (DIP) value, the controller goes to step 8
Usually, a minimal increase in pressure, such as 1 or 2 
psi, is desirable.

8  The controller counts down the DELAY CLOSE TIME 

(SET 08). When the DELAY CLOSE TIME countdown 
reaches zero, the controller checks the casing 
pressure again to see if it has still increased by the 
DIFFERENTIAL CLOSE PRESSURE (DIP) value.

If the increase is a brief spike in pressure, the 

 

ƒ

controller continues the DELAY TIME (SALES) 
countdown. The controller goes back to step 7.
If the increase is an actual or solid pressure 

 

ƒ

increase, the controller goes back to step 1.

Summary of Contents for PCS 4000

Page 1: ...e Transducers Reporting Wireless to the Controller 8 Turn off a Transducer 8 Creating a Pressure Operation Plunger Program 9 Pressure Operation Selection Functions 9 Pressure Operation Control Functions 9 Features for Opening the A Valve 11 Features for Closing the A Valve 12 Features for Special Circumstances 12 Sales Line Safeguard Features 13 Using Pressure Operation to Intermit a Well without ...

Page 2: ...N A Valve Open Time OFF Close Time B ON B Valve Open Time 00 Battery And Solar Conditions 02 A Valve Delay Sales Time 03 Mandatory Shut In Time 05 Plunger Fall Time 08 Delay Close Time Sensor Status On or Off 09 Auxillary Close Delay On No Delay or Off Close Delay 11 Controller Operating Mode Differential Open Pressure 12 Casing Tubing or Casing Line 13 Casing PSI Increase Casing Dip Close 14 High...

Page 3: ...si Example 00100 Depending on the setting of the METRIC function SET 33 the unit of measurement for flow rate is either thousand cubic feet mcf or thousand cubic meters E3 M3 Operating the A Valve and B Valve Manually Open the A Valve ON Press ON ON overrides all programmed functions such as FALL TIME and MANDATORY SHUT IN TIME ON does not override safeguard functions such as LOW LINE CLOSE PRESSU...

Page 4: ...lay its current value press READ B 0 Program Function SET or READ Display Name Page Status of A Valve when B Valve Is Open B0 A OPEN W B VAL 9 Program Function SET or READ Display Name Page OPEN TIME ON A OPEN TIME 9 CLOSE TIME OFF CLOSE TIME 11 DELAY TIME SALES 02 A DELAY TIME 13 MANDATORY SHUT IN TIME 03 MAND SHUT IN 10 B OPEN TIME B ON B OPEN TIME 9 B DELAY TIME B2 B DELAY TIME 13 FALL TIME 05 ...

Page 5: ...ger Counts History READ 04 This report shows how many times the A valve opened and how many times the plunger arrived while the A valve was open Example A PLUNGER 92 A VALVE 96 In the example A VALVE 96 shows that the A valve opened 96 times A PLUNGER 92 shows that the plunger arrived 92 times while the A valve was open 96 92 4 The plunger did not arrive 4 times while the A valve was open Note If ...

Page 6: ...open time ran out S increase in casing pressure input U drop in casing pressure input CLS information shows How long the A valve was closed A letter that explains why the A valve opened C CLOSE TIME counted down to zero D differential open pressure input M manual open R load factor input T casing time input Note If the A valve opens because a close input stops there is no letter For example the A ...

Page 7: ... TIME SET ON If the plunger arrives during the OPEN TIME countdown the controller goes to step 6 If the plunger does not arrive during the OPEN TIME countdown the controller goes to step 5 5 The controller opens the optional B valve and counts down the B OPEN TIME SET B ON If the plunger arrives during the B OPEN TIME countdown the controller goes to step 6 If the plunger does not arrive during OP...

Page 8: ...n accurate pressure gauge to obtain the pressure value for the next step Press SET 17 ON OFF ON enter the pressure value For example if the current tubing pressure is 200 psi enter 00200 Sales Line Transducer Calibration If the sales line transducer is wired directly to the controller Calibrate the sales line transducer for the low pressure 1 With transducer in place remove pressure Press SET 18 O...

Page 9: ... valve to be either open or closed when the B valve is open To keep A valve open when B valve is open press ON To close A valve when B valve is open press OFF Pressure Operation Control Functions FALL TIME SET 05 FALL TIME guarantees a minimum shut in time for the plunger to fall to the bottom of the well DIFFERENTIAL OPEN PRESSURE SET 12 DIFFERENTIAL OPEN PRESSURE is the pressure value that must ...

Page 10: ...d closes the well when the casing pressure rises to 153 psi If the DIFFERENTIAL CLOSE PRESSURE DIP is 10 psi the controller stops the sale of gas and closes the well when the casing pressure rises to 160 psi A good DIFFERENTIAL CLOSE PRESSURE DIP setting for many wells is 1 2 or 3 psi The casing pressure flutters up and down as it falls For example the casing pressure may go 160 159 160 159 158 15...

Page 11: ... counts down the CASING PEAK TIME the display shows CLOSE 0 00 00 Typical CASING PEAK TIME values for a well with casing pressure that builds fast are 10 12 minutes For a well with casing pressure that builds slowly a typical value is 30 minutes Note You can use both DIFFERENTIAL OPEN PRESSURE and CASING PEAK TIME to control the well If you want to use only CASING PEAK TIME to open the well set th...

Page 12: ...W RATE Example Set the B LOW FLOW RATE to 50 The controller opens the B valve when the flow rate falls below 50 mcf B LOW FLOW DELAY TIME SET 36 If you are using B LOW FLOW RATE you can use B LOW FLOW DELAY TIME to keep the controller from opening the B valve if there is a brief drop in flow rate Typical settings for B LOW FLOW DELAY TIME are 1 to 2 minutes Features for Special Circumstances CASIN...

Page 13: ... LINE CLOSE PRESSURE is reached during B OPEN TIME which is used to vent the well the controller does not close the B valve DELAY LINE CLOSE TIME SET B8 If you are using HIGH LINE CLOSE PRESSURE LOW LINE CLOSE PRESSURE or both you can use DELAY LINE CLOSE TIME to keep the controller from shutting in the well if there is a brief spike or drop in sales line pressure Brief spikes in pressure often oc...

Page 14: ...See CASING PEAK TIME on page 11 Features for Closing the A Valve In addition to the basic functions for intermitting a well with pressure operation you can use any of the features for closing the A valve For more information see Features for Closing the A Valve on page 12 Features for Special Circumstances CASING DROP PRESSURE SET 20 Because the well does not have a plunger the controller can t st...

Page 15: ...nk call your PCS sales and service representative If the controller s display is now working and if you 5 replaced the battery check the manufacture date on the battery If the battery is less than 3 years old check the solar panel Go to Test 3 Test 3 Check solar panel Disconnect the solar panel from the terminals Use a 1 volt meter to obtain the voltage and amperage A good solar panel reading in f...

Page 16: ...solar panel Go to Test 3 If the controller still won t run the program cycle or open the motor valve go to Test 4 Test 3 Check solar panel Disconnect the solar panel from the terminals Use a 1 volt meter to obtain the voltage and amperage A good solar panel reading in full sun exposure is 10 7 volts and 350 430 mA If the solar panel is defective change it 2 Check the solar panel installation 3 The...

Page 17: ...through the sensor band If the controller goes to DELAY TIME SALES the problem may be a wellhead electrical current Go to step 4 4 Possible causes of a wellhead electrical problem The sensor or sensor wire may be defective or The well may need PCS newest style 2 coil sensor This sensor is available in 2 wire or 3 wire connections 5 Call your PCS sales and service representative Short term fix for ...

Page 18: ... page 12 Plunger has surfaced but Plunger Travel Time History READ 06 shows C instead of A or B Make sure sensor is turned on Press READ 09 The controller s display should show SENSOR ON If the display shows SENSOR ON go to Test 1 If the display shows SENSOR OFF press SET 09 and then press ON Go to Test 3 step 2 Test 1 Check CASING DROP PRESSURE Press READ 20 1 Make sure the CASING DROP PRESSURE i...

Page 19: ...olar panel is defective change it 2 Check the solar panel installation 3 The solar panel should face south The tilt of the solar panel should be the latitude of the location plus 15 degrees Example if the latitude is 45 degrees tilt the solar panel 60 degrees with respect to the horizon The element should be free from dirt oil and so on Check for cracks in the solar panel Check whether the solar p...

Page 20: ...uyer only Warranty is completely void if abuse neglect misuse or misapplication is the cause of the malfunction Determination of abuse or damage to be made solely by PCS PCS 4000 is a trademark of Production Control Services Inc Copyright 2008 Production Control Services Inc All rights reserved 5 22 08 You can get more information about the PCS products at ProductionControlServices com PCS 4000 SI...

Reviews: