PCS PCS 4000 User Manual Download Page 11

USER GUIDE

11

PCS 4000 

SINGLE WELL CONTROLLER

Features for Opening the A-Valve

CLOSE TIME = 

 

SET OFF

CLOSE TIME is normally set to 00:00:00 because the 
controller opens the A-valve in response to changes in 
pressure.

If you want to open the A-valve after a period of time, 
regardless of pressure changes, you can set the CLOSE 
TIME. If you do program a CLOSE TIME, make sure to set 
the time no lower than your FALL TIME. This will ensure 
that the plunger has time to reach the bottom of the 
tubing before the controller opens the A-valve.

If the controller opens the well when the CLOSE TIME 
countdown reaches zero, you are using the controller to 
operate the well based on time instead of pressure.

CASING PEAK TIME = 

 

SET 21

CASING PEAK TIME is normally set to 99:00:00 when the 
feature is not used.

When you use this feature, the controller opens the 
A-valve after the casing pressure peaks. The controller 
monitors the casing pressure independently of the 
DIFFERENTIAL OPEN PRESSURE. The controller counts 
down the CASING PEAK TIME. It restarts the countdown 
whenever the casing pressure increases by 1 psi.

For example, the CASING PEAK TIME is 10 minutes. 
When the A-valve closes, the controller counts down 
the CASING PEAK TIME. If the casing pressure builds 
1 psi within 10 minutes and the FALL TIME has reached 
zero, the controller restarts the CASING PEAK TIME 
countdown. If the casing pressure does not build 1 psi 
within 10 minutes, the controller counts down the 
CASING PEAK TIME to zero. It then checks the FALL 
TIME countdown. It opens the A-valve when both the 
CASING PEAK TIME and FALL time countdowns have 
reached zero.

Note:

 While the controller counts down the CASING PEAK 

TIME, the display shows CLOSE 0:00:00.

Typical CASING PEAK TIME values for a well with casing 
pressure that builds fast are 10-12 minutes. For a well 
with casing pressure that builds slowly, a typical value is 
30 minutes.

Note: 

You can use both DIFFERENTIAL OPEN PRESSURE 

and CASING PEAK TIME to control the well. If you want 
to use only CASING PEAK TIME to open the well, set the 
DIFFERENTIAL OPEN PRESSURE to a high value that will 
never be reached.

LOAD FACTOR = 

 

SET 24

LOAD FACTOR is a feature used with Mode 2 (tubing 
pressure minus line pressure) or Mode 4 (casing pressure 
minus line pressure). Load Factor helps insure that the 
liquid load in the tubing is less than the energy needed to 
lift the load to surface. When Load Factor is enabled, the 
controller will not open the well until 2 set points are met:

The controller compares the line pressure to the tubing 

 

„

pressure (Mode 2) or the casing pressure (Mode 4).
In both modes, the controller compares casing, tubing, 

 

„

and line pressures as a ratio to determine the net lifting 
energy. See the calculation below.

When both set points and all other “open” criteria are met, 
the controller opens the well to production.

A well’s load factor is the ratio of casing pressure minus 
tubing pressure to casing pressure minus line pressure.

LOAD FACTOR = Casing Pressure - Tubing Pressure 
                             Casing Pressure - Line Pressure

If you set the LOAD FACTOR to 50, the controller opens 
the A-valve when the ratio is 50% or lower (and the other 
“open” criteria have been met).

Example:

Casing Pressure - Tubing Pressure = 100 psi

 

„

Casing Pressure - Line Pressure     = 500 psi

 

„

100/500 = 20%

 

„

If the LOAD FACTOR is set to 20% or a lower value, 

 

„

the controller opens the A-valve.

Normal values for LOAD FACTOR range from 40% to 
60% depending on the well’s individual characteristics.

If you are not using LOAD FACTOR, set it to 00 percent.

Summary of Contents for PCS 4000

Page 1: ...e Transducers Reporting Wireless to the Controller 8 Turn off a Transducer 8 Creating a Pressure Operation Plunger Program 9 Pressure Operation Selection Functions 9 Pressure Operation Control Functions 9 Features for Opening the A Valve 11 Features for Closing the A Valve 12 Features for Special Circumstances 12 Sales Line Safeguard Features 13 Using Pressure Operation to Intermit a Well without ...

Page 2: ...N A Valve Open Time OFF Close Time B ON B Valve Open Time 00 Battery And Solar Conditions 02 A Valve Delay Sales Time 03 Mandatory Shut In Time 05 Plunger Fall Time 08 Delay Close Time Sensor Status On or Off 09 Auxillary Close Delay On No Delay or Off Close Delay 11 Controller Operating Mode Differential Open Pressure 12 Casing Tubing or Casing Line 13 Casing PSI Increase Casing Dip Close 14 High...

Page 3: ...si Example 00100 Depending on the setting of the METRIC function SET 33 the unit of measurement for flow rate is either thousand cubic feet mcf or thousand cubic meters E3 M3 Operating the A Valve and B Valve Manually Open the A Valve ON Press ON ON overrides all programmed functions such as FALL TIME and MANDATORY SHUT IN TIME ON does not override safeguard functions such as LOW LINE CLOSE PRESSU...

Page 4: ...lay its current value press READ B 0 Program Function SET or READ Display Name Page Status of A Valve when B Valve Is Open B0 A OPEN W B VAL 9 Program Function SET or READ Display Name Page OPEN TIME ON A OPEN TIME 9 CLOSE TIME OFF CLOSE TIME 11 DELAY TIME SALES 02 A DELAY TIME 13 MANDATORY SHUT IN TIME 03 MAND SHUT IN 10 B OPEN TIME B ON B OPEN TIME 9 B DELAY TIME B2 B DELAY TIME 13 FALL TIME 05 ...

Page 5: ...ger Counts History READ 04 This report shows how many times the A valve opened and how many times the plunger arrived while the A valve was open Example A PLUNGER 92 A VALVE 96 In the example A VALVE 96 shows that the A valve opened 96 times A PLUNGER 92 shows that the plunger arrived 92 times while the A valve was open 96 92 4 The plunger did not arrive 4 times while the A valve was open Note If ...

Page 6: ...open time ran out S increase in casing pressure input U drop in casing pressure input CLS information shows How long the A valve was closed A letter that explains why the A valve opened C CLOSE TIME counted down to zero D differential open pressure input M manual open R load factor input T casing time input Note If the A valve opens because a close input stops there is no letter For example the A ...

Page 7: ... TIME SET ON If the plunger arrives during the OPEN TIME countdown the controller goes to step 6 If the plunger does not arrive during the OPEN TIME countdown the controller goes to step 5 5 The controller opens the optional B valve and counts down the B OPEN TIME SET B ON If the plunger arrives during the B OPEN TIME countdown the controller goes to step 6 If the plunger does not arrive during OP...

Page 8: ...n accurate pressure gauge to obtain the pressure value for the next step Press SET 17 ON OFF ON enter the pressure value For example if the current tubing pressure is 200 psi enter 00200 Sales Line Transducer Calibration If the sales line transducer is wired directly to the controller Calibrate the sales line transducer for the low pressure 1 With transducer in place remove pressure Press SET 18 O...

Page 9: ... valve to be either open or closed when the B valve is open To keep A valve open when B valve is open press ON To close A valve when B valve is open press OFF Pressure Operation Control Functions FALL TIME SET 05 FALL TIME guarantees a minimum shut in time for the plunger to fall to the bottom of the well DIFFERENTIAL OPEN PRESSURE SET 12 DIFFERENTIAL OPEN PRESSURE is the pressure value that must ...

Page 10: ...d closes the well when the casing pressure rises to 153 psi If the DIFFERENTIAL CLOSE PRESSURE DIP is 10 psi the controller stops the sale of gas and closes the well when the casing pressure rises to 160 psi A good DIFFERENTIAL CLOSE PRESSURE DIP setting for many wells is 1 2 or 3 psi The casing pressure flutters up and down as it falls For example the casing pressure may go 160 159 160 159 158 15...

Page 11: ... counts down the CASING PEAK TIME the display shows CLOSE 0 00 00 Typical CASING PEAK TIME values for a well with casing pressure that builds fast are 10 12 minutes For a well with casing pressure that builds slowly a typical value is 30 minutes Note You can use both DIFFERENTIAL OPEN PRESSURE and CASING PEAK TIME to control the well If you want to use only CASING PEAK TIME to open the well set th...

Page 12: ...W RATE Example Set the B LOW FLOW RATE to 50 The controller opens the B valve when the flow rate falls below 50 mcf B LOW FLOW DELAY TIME SET 36 If you are using B LOW FLOW RATE you can use B LOW FLOW DELAY TIME to keep the controller from opening the B valve if there is a brief drop in flow rate Typical settings for B LOW FLOW DELAY TIME are 1 to 2 minutes Features for Special Circumstances CASIN...

Page 13: ... LINE CLOSE PRESSURE is reached during B OPEN TIME which is used to vent the well the controller does not close the B valve DELAY LINE CLOSE TIME SET B8 If you are using HIGH LINE CLOSE PRESSURE LOW LINE CLOSE PRESSURE or both you can use DELAY LINE CLOSE TIME to keep the controller from shutting in the well if there is a brief spike or drop in sales line pressure Brief spikes in pressure often oc...

Page 14: ...See CASING PEAK TIME on page 11 Features for Closing the A Valve In addition to the basic functions for intermitting a well with pressure operation you can use any of the features for closing the A valve For more information see Features for Closing the A Valve on page 12 Features for Special Circumstances CASING DROP PRESSURE SET 20 Because the well does not have a plunger the controller can t st...

Page 15: ...nk call your PCS sales and service representative If the controller s display is now working and if you 5 replaced the battery check the manufacture date on the battery If the battery is less than 3 years old check the solar panel Go to Test 3 Test 3 Check solar panel Disconnect the solar panel from the terminals Use a 1 volt meter to obtain the voltage and amperage A good solar panel reading in f...

Page 16: ...solar panel Go to Test 3 If the controller still won t run the program cycle or open the motor valve go to Test 4 Test 3 Check solar panel Disconnect the solar panel from the terminals Use a 1 volt meter to obtain the voltage and amperage A good solar panel reading in full sun exposure is 10 7 volts and 350 430 mA If the solar panel is defective change it 2 Check the solar panel installation 3 The...

Page 17: ...through the sensor band If the controller goes to DELAY TIME SALES the problem may be a wellhead electrical current Go to step 4 4 Possible causes of a wellhead electrical problem The sensor or sensor wire may be defective or The well may need PCS newest style 2 coil sensor This sensor is available in 2 wire or 3 wire connections 5 Call your PCS sales and service representative Short term fix for ...

Page 18: ... page 12 Plunger has surfaced but Plunger Travel Time History READ 06 shows C instead of A or B Make sure sensor is turned on Press READ 09 The controller s display should show SENSOR ON If the display shows SENSOR ON go to Test 1 If the display shows SENSOR OFF press SET 09 and then press ON Go to Test 3 step 2 Test 1 Check CASING DROP PRESSURE Press READ 20 1 Make sure the CASING DROP PRESSURE i...

Page 19: ...olar panel is defective change it 2 Check the solar panel installation 3 The solar panel should face south The tilt of the solar panel should be the latitude of the location plus 15 degrees Example if the latitude is 45 degrees tilt the solar panel 60 degrees with respect to the horizon The element should be free from dirt oil and so on Check for cracks in the solar panel Check whether the solar p...

Page 20: ...uyer only Warranty is completely void if abuse neglect misuse or misapplication is the cause of the malfunction Determination of abuse or damage to be made solely by PCS PCS 4000 is a trademark of Production Control Services Inc Copyright 2008 Production Control Services Inc All rights reserved 5 22 08 You can get more information about the PCS products at ProductionControlServices com PCS 4000 SI...

Reviews: